10.5Setting values for converter control

P080

Control word for brake control

*

1

The brake is a holding brake

 

(G140)

 

When the "Operating enable" command is cancelled or when

 

the "Voltage disconnection" or "E-Stop" command is input, the

 

 

 

 

"Close brake" command is not input until n< nmin (P370, P371)

 

 

is reached.

2The brake is an operating brake

When the "Operating enable" command is cancelled or when the "Voltage disconnection" or "E-Stop" command is input, the "Close brake" command is input immediately, i.e. while the motor is still rotating.

P081

EMF-dependent field weakening

*

0

No field-weakening operation as a function of speed or EMF

 

 

 

(100% of rated motor field current is applied constantly as the

(G165)

 

internal field current setpoint).

1Field-weakening operation by internal closed-loop EMF control to ensure that in field-weakening operation, i.e. at speeds above the motor rated speed (="field-weakening activation limit speed”), the motor EMF is maintained constantly at the setpoint EMFset (K0289) = P101 – P100 * P110 (field current setpoint is the product of the EMF controller output and the precontrol component determined by the actual speed according to the field characteristic).

NOTICE

When P081=1, a valid field characteristic must be available (P117=1), otherwise the optimization run for field weakening (P051=27) must be executed.

1 to 2

0 to 1

1

Ind: None

P052

= 3

FS=1

P051

= 40

Type: O2

Offline

Ind: None

P052

= 3

FS=0

P051

= 40

Type: L2

Offline

SIEMENS Energy & Automation

10-17

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 138
Image 138
Siemens 6RA70 specifications Setting values for converter control, 10-17, P080 Control word for brake control