Siemens 6RA70 F078, F079 SCB1 Telegram failure, F080 Error in initialization of a CB/TB board

Models: 6RA70

1 232
Download 232 pages 59.99 Kb
Page 115
Image 115

Fault

 

Description

 

 

No.

 

 

Cause as a function of fault value

 

 

Further information (r047.002 to r047.016)

 

 

 

 

(r047.001, r949.001 or r949.009 with acknowledged error)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F078

SCB1: Current below 4mA minimum value at analog input3 of slave 2

 

 

 

 

(active in all operating states)

 

 

 

 

 

The cause of the fault may be a cable break

 

 

 

 

 

 

 

 

F079

SCB1: Telegram failure

 

 

 

 

 

(active in all operating states)

 

 

 

 

 

Check function of SCB1 (activity LEDs) and connection to SCI slaves (fiber optics)

 

 

 

 

 

F080

Error in initialization of a CB/TB board

 

 

 

 

 

Possible causes for fault values 1 and 6:

 

 

 

 

 

CB/TB board is defective

 

 

 

 

 

CB/TB board is not installed correctly

 

 

 

 

 

CB/TB board is taking too long to run up (e.g. due to very complex TB configuration)

 

 

Fault value (r949 index 001):

r047 index 002 to 016:

 

 

 

 

 

 

 

1

The "Heartbeat counter“ of the CB/TB has not started to

i015 Code number of board:

 

 

 

count within 20 s

1

TB or 1st CB

 

 

 

 

 

2

2nd CB

 

 

2

The product version of the installed CT/TB board is not

i002 Code number of slot containing incompatible board:

 

 

 

compatible with the SIMOREG 6RA70 converter

2

Slot D

 

 

 

 

 

3

Slot E

 

 

 

 

 

4

Slot F

 

 

 

 

 

5

Slot G

 

 

 

 

 

6

CB when configuration includes TB

 

 

 

 

 

 

 

5

Parameters P918, U711 to U721 are not correctly set or

i015 Code number of board:

 

 

 

not accepted after a change by means of U710 = 0

1

TB or 1st CB

 

 

 

setting. (The meanings of these parameters are defined

2

2nd CB

 

 

 

in the manual for the relevant CB board, see also function

 

 

 

 

 

 

diagrams, Section 8, Sheets Z110 and Z111)

 

 

 

 

 

 

 

 

 

 

6

The initialization run for a CB/TB board has not been

i015 Code number of board:

 

 

 

completed within 40 s

1

TB or 1st CB

 

 

 

 

 

2

2nd CB

F081

CB/TB heartbeat error

i015 Code number of board:

 

 

CB/TB has not incremented the monitoring counter for a period

1

TB or 1st CB

 

 

2

2nd CB

 

 

of 800 ms

 

 

 

 

 

 

 

Possible causes of fault

 

 

 

 

 

CB/TB board is defective

 

 

 

 

 

CB/TB board is not correctly installed

 

 

 

 

 

 

 

 

F082

CB/TB message timeout or error in data exchange

 

 

 

 

 

Possible causes of fault

 

 

 

 

 

CB/TB PZD message timeout (with fault value 10)

 

 

 

 

 

Excessive EMC-related interference

 

 

 

 

 

 

(e.g. due to unprotected contactors, unscreened cables, loose screen connections)

 

 

CB/TB board is defective

 

 

 

 

 

CB/TB board is not correctly inserted

 

 

 

 

 

Fault value (r949 index 001):

r047 Index 002 to 016:

 

 

 

 

 

 

 

1

Fault in alarm channel from CB to basic unit

i015 Code number of board:

 

 

 

 

 

1

TB or 1st CB

 

 

 

 

 

2

2nd CB

 

 

2

Fault in alarm channel from TB to basic unit

 

 

 

 

 

 

 

 

 

 

 

 

3

Fault in fault channel from TB to basic unit

 

 

 

 

 

 

 

 

 

 

5

Fault in parameter job channel from CB to basic unit

i015 Code number of board:

 

 

 

 

 

1

TB or 1st CB

 

 

 

 

 

2

2nd CB

 

 

6

Fault in parameter response channel from basic unit to

i015 Code number of board:

 

 

CB

1

1st TB or 1st CB

 

 

 

 

 

2

2nd CB

 

 

7

Fault in parameter job channel from TB to basic unit

 

 

 

 

 

 

 

 

 

 

9-26

 

 

 

 

 

Siemens Energy & Automation

 

 

 

 

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 115