Siemens 6RA70 Ramp-function generator, 10-39, P295 Mode for rounding the ramp-function generator

Models: 6RA70

1 232
Download 232 pages 59.99 Kb
Page 160
Image 160

 

PNU

Description

Value range

No. indices

See

 

 

 

 

[Unit]

Factory

Change

 

 

 

 

Steps

setting

(Access /

 

 

 

 

 

Type

Status)

 

P284

Set EMF controller P component to zero

0 to 1

Ind: 4

P052 = 3

*

0

Set controller P component to zero

1

FS=1

P051 = 40

 

FDS

 

Type: O2

Offline

 

 

(i.e. to obtain pure I controller)

 

 

(G165)

 

 

 

 

 

1

Controller P component is active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.14 Ramp-function generator

(see also Section 8, Sheet G136 and Section 9 of Operating Instructions 6RX1700-0AD**) See P639 and P640 for ramp-function generator setting parameters

P295

Mode for rounding the ramp-function generator

[SW 1.9 and later]

FDS

0

If the setpoint is reversed during ramp-up (or ramp-down),

 

acceleration (deceleration) is aborted and initial rounding of the

 

 

(G136)

 

deceleration (acceleration) process begins immediately. The

 

 

setpoint is not increased (decreased) any further, but the signal

 

 

at the ramp-function generator output has a breakpoint (i.e. a

 

 

step change in the acceleration rate).

 

 

 

Ramp generator

 

 

 

output

 

 

 

Ramp generator

 

 

 

input

 

1If the setpoint is reversed during ramp-up or ramp-down, acceleration/deceleration gradually changes to deceleration/acceleration. The setpoint increases/decreases further, but there is no breakpoint in the signal at the generator output (i.e. there is no step change in the acceleration rate).

 

Ramp generator

 

output

 

Ramp generator

 

input

 

 

P296

Ramp-down time of ramp generator with quick stop (OFF3)

FDS

[SW 1.9 and later]

When the "quick stop" command is issued, the drive must normally

(G136)

brake down to 0 speed along the current limit. If the mechanical design of

 

 

the drive makes this option impermissible or undesirable, then a value of > 0

 

can be set here. In this case, the drive brakes along the deceleration ramp

 

programmed here when the "quick stop" command is issued.

 

see also parameter P330

 

 

P297

Lower transition rounding of ramp generator with quick stop (OFF3)

FDS

[SW 1.9 and later]

see also parameter P330

(G136)

 

P298

Upper transition rounding of ramp generator with quick stop (OFF3)

FDS

[SW 1.9 and later]

see also parameter P330

(G136)

 

0 to 1

1

0.00to 650.00

[s]

0.01s

0.00to 100.00

[s]

0.01s

0.00to 100.00

[s]

0.01s

Ind: 4

P052

= 3

FS=0

P051

= 40

Type: O2

on-line

Ind: 4

P052

= 3

FS=0.00

P051

= 40

Type: O2

on-line

Ind: 4

P052

= 3

FS=0.00

P051

= 40

Type: O2

on-line

 

 

 

Ind: 4

P052

= 3

FS=0.00

P051

= 40

Type: O2

on-line

SIEMENS Energy & Automation

10-39

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 160
Image 160
Siemens 6RA70 specifications Ramp-function generator, 10-39, P295 Mode for rounding the ramp-function generator