PNU

Description

Value range

No. indices

See

 

 

 

 

[Unit]

Factory

Change

 

 

 

 

Steps

setting

(Access /

 

 

 

 

 

Type

Status)

 

P163

EMF filtering method for armature precontrol

0 to 3

Ind: 4

P052 = 3

*

0

No filtering

1

FS=3

P051 = 40

 

FDS

 

Type: O2

Offline

 

1

Filtering element, filter time constant = approx. 10 ms

 

 

 

 

 

 

 

 

 

 

 

(G162)

 

(for use by works engineers only)

 

 

 

 

2

Averaging over the last 2 EMF values

 

 

 

 

 

 

 

 

 

 

 

(for use by works engineers only )

 

 

 

 

 

3

Averaging over the last 3 EMF values

 

 

 

 

 

 

 

 

 

 

P164

Set armature current controller P component to zero

0 to 1

Ind: 4

P052 = 3

*

0

Set controller P component to zero (i.e. to obtain pure I

1

FS=1

P051 = 40

 

FDS

 

Type: O2

Offline

 

 

controller)

 

 

(G162)

 

 

 

 

 

1

Controller P component is active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P165

Select the binector to control the "Enable a torque direction for torque

All binector numbers

Ind: 2

P052 = 3

*

direction change" function

1

FS=220

P051 = 40

 

BDS

 

 

 

Type: L2

Offline

 

 

 

 

 

 

 

(G163)

0

= Binector B0000

 

 

 

 

 

 

 

 

 

 

1

= Binector B0001

 

 

 

 

 

etc.

 

 

 

 

 

Binector status =

 

 

 

 

 

0

... Enable for M0 or MII

 

 

 

 

 

1 ... Enable for M0 or MI

 

 

 

 

 

 

 

 

 

 

10.9Current limitation, torque limitation

P169

Select closed-loop torque / current control

 

0 to 1

Ind: 4

P052

= 3

*

See parameter P170

 

1

FS=1

P051

= 40

FDS

 

 

Type: O2

Offline

 

 

 

 

 

(G160)

 

 

 

 

 

 

 

 

P170

Select closed-loop torque / current control

 

0 to 1

Ind: 4

P052

= 3

*

P169

P170

 

 

1

FS=0

P051

= 40

FDS

 

 

 

Type: O2

Offline

0

0

Closed-loop current control and current limitation

 

 

 

 

 

 

 

 

 

 

(G160)

0

1

Closed-loop torque control with torque limitation (the

 

 

 

 

 

 

torque setpoint is converted to a current setpoint: Current

 

 

 

 

 

 

 

setpoint = torque setpoint / motor flux)

 

 

 

 

 

 

 

Current limitation is active additionally

 

 

 

 

 

1

0

Closed-loop current control with torque limitation (the

 

 

 

 

 

 

 

specified torque limit is converted to a current limit:

 

 

 

 

 

 

 

Current limit = torque limit / motor flux)

 

 

 

 

 

 

 

Current limitation is active additionally

 

 

 

 

 

1

1

Do not set!

 

 

 

 

 

 

Note:

 

 

 

 

 

 

 

 

A valid field characteristic (P117=1) must be available when P169 or

 

 

 

 

 

P170=1. If one is not, the optimization run for field weakening (P051=27)

 

 

 

 

 

must be executed.

 

 

 

 

 

 

P263 determines the input quantity for the motor flux calculation.

 

 

 

 

 

 

 

 

 

 

 

P171

System current limit in torque direction I

 

0.0 to 300.0

Ind: 4

P052

= 3

FDS

 

 

 

 

[% of P100]

FS=100.0

P051

= 40

(G160)

 

 

 

 

0.1% of P100

Type: O2

Online

(G161)

 

 

 

 

 

 

 

 

P172

System current limit in torque direction II

 

-300.0 to 0.0

Ind: 4

P052

= 3

FDS

 

 

 

 

[% of P100]

FS=-100.0

P051

= 40

(G160)

 

 

 

 

0.1% of P100

Type: I2

Online

(G161)

 

 

 

 

 

 

 

 

P173

Source for "Torque control / Current control" switchover

All binector numbers

Ind: 2

P052

= 3

*

 

 

 

[SW 1.9 and later]

1

FS=0

P051

= 40

BDS

The binector selected here has the same effect as parameter P170.

 

Type: L2

Offline

 

 

 

 

(G160)

0 = binector B0000

 

 

 

 

 

1 = binector B0001

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P175

Source for variable P gain

[SW 1.8 and later]

All connector

Ind: 4

P052

= 3

*

 

 

 

 

numbers

FS=1

P051

= 40

FDS

The content of the selected connector acts as the

P gain for the armature

1

Type: L2

off-line

(G162)

 

 

 

 

current controller after multiplication with P155.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10-32

 

 

 

 

SIEMENS Energy & Automation

 

 

 

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 153
Image 153
Siemens 6RA70 specifications Current limitation, torque limitation, 10-32