PNU

 

Description

 

Value range

 

 

No. indices

 

See

 

 

 

 

 

 

[Unit]

 

 

Factory

 

Change

 

 

 

 

 

 

Steps

 

 

setting

 

(Access /

 

 

 

 

 

 

 

 

 

Type

 

Status)

 

P492

 

Analog monitoring of motor temperature: Trip temperature

 

0 to 200

 

 

Ind: 4

 

P052 = 3

 

FDS

 

Operative only when P490.x=1.

 

[°C]

 

 

FS=0

 

P051 = 40

 

(G185)

 

 

1°C

 

 

Type: O2

 

Online

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P493

 

Motor temperature analog 1 (temperature sensor at terminals 22 / 23):

0 to 3

 

Ind: 4

P052 = 3

*

 

Tripping of alarm or fault message

1

 

FS=0

P051 = 40

 

FDS

 

Motor temperature grasped with KTY84

 

 

 

Type: O2

Offline

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(G185)

0

Monitoring deactivated

 

 

 

 

 

 

 

 

 

1

Alarm (A029) at temperature > P491

 

 

 

 

 

 

 

 

 

2

Fault message (F029) at temperature > P492

 

 

 

 

 

 

 

 

 

3

Alarm (A029) at temperature > P491 and

 

 

 

 

 

 

 

 

 

 

 

fault message (F029) at temperature > P492

 

 

 

 

 

 

 

 

 

Motor temperature grasped with PTC thermistor

 

 

 

 

 

 

 

 

 

0

Monitoring deactivated

 

 

 

 

 

 

 

 

 

1

Alarm message (A029) when operating point of PTC thermistor

 

 

 

 

 

 

 

 

 

 

 

is reached

 

 

 

 

 

 

 

 

 

2

Fault message (F029) when operating point of PTC thermistor is

 

 

 

 

 

 

 

 

 

 

 

reached

 

 

 

 

 

 

 

 

 

3

Illegal setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P494

 

Motor temperature analog 2 (temperature sensor at terminals 204 /

0 to 3

 

Ind: 4

P052 = 3

*

 

205): Tripping of alarm or fault message

1

 

FS=0

P051 = 40

 

FDS

 

Motor temperature grasped with KTY84

 

 

 

Type: O2

Offline

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(G185)

0

Monitoring deactivated

 

 

 

 

 

 

 

 

1

Alarm (A029) at temperature > P491

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Fault message (F029) at temperature > P492

 

 

 

 

 

 

 

 

 

3

Alarm (A029) at temperature > P491 and

 

 

 

 

 

 

 

 

 

 

 

fault message (F029) at temperature > P492

 

 

 

 

 

 

 

 

 

Motor temperature grasped with PTC thermistor

 

 

 

 

 

 

 

 

 

0

Monitoring deactivated

 

 

 

 

 

 

 

 

 

1

Alarm message (A029) when operating point of PTC thermistor

 

 

 

 

 

 

 

 

 

 

 

is reached

 

 

 

 

 

 

 

 

 

2

Fault message (F029) when operating point of PTC thermistor is

 

 

 

 

 

 

 

 

 

 

 

reached

 

 

 

 

 

 

 

 

 

3

Illegal setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P495

 

Brush length sensing: Tripping of alarm or fault message

 

0 to 2

 

Ind: 4

P052 = 3

*

0

No brush length sensing (terminal 211 is not scanned)

1

 

FS=0

P051 = 40

 

FDS

 

 

 

Type: O2

Offline

 

1

Binary brush length sensing (terminal 211 is scanned)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(G186)

 

 

Alarm (A025) in response to 0 signal

 

 

 

 

 

 

 

 

2

Binary brush length sensing (terminal 211 is scanned)

 

 

 

 

 

 

 

 

 

 

 

Fault message (F025) in response to 0 signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P496

 

Bearing condition: Tripping of alarm or fault message

 

0 to 2

 

Ind: 4

P052 = 3

*

0

No bearing condition sensing (terminal 212 is not scanned)

1

 

FS=0

P051 = 40

 

FDS

 

 

 

Type: O2

Offline

 

1

Bearing condition sensing (terminal 212 is scanned)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(G186)

 

 

Alarm (A026) in response to 1 signal

 

 

 

 

 

 

 

 

2

Bearing condition sensing (terminal 212 is scanned)

 

 

 

 

 

 

 

 

 

 

 

Fault message (F026) in response to 1 signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P497

 

Air flow: Tripping of alarm or fault message

 

0 to 2

 

Ind: 4

P052 = 3

*

0

No air flow monitoring (terminal 213 is not scanned)

1

 

FS=0

P051 = 40

 

FDS

 

 

 

Type: O2

Offline

 

1

Air flow monitoring (terminal 213 is scanned)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(G186)

 

 

Alarm (A027) in response to 0 signal

 

 

 

 

 

 

 

 

2

Air flow monitoring (terminal 213 is scanned)

 

 

 

 

 

 

 

 

 

 

 

Fault message (F027) in response to 0 signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P498

 

Temperature switch: Tripping of alarm or fault message

 

0 to 2

 

Ind: 4

P052 = 3

*

0

No temperature switch connected (terminal 214 is not scanned)

1

 

FS=0

P051 = 40

 

FDS

 

 

 

Type: O2

Offline

 

1

Temperature switch connected (terminal 214 is scanned)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(G186)

 

 

Alarm (A028) in response to 0 signal

 

 

 

 

 

 

 

 

2

Temperature switch connected (terminal 214 is scanned)

 

 

 

 

 

 

 

 

 

 

 

Fault message (F028) in response to 0 signal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10-52

 

 

 

 

 

SIEMENS Energy & Automation

 

 

 

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 173
Image 173
Siemens 6RA70 specifications 10-52, P496 Bearing condition Tripping of alarm or fault message