Fault

No.

 

Description

 

 

 

Cause as a function of fault value

 

 

Further information (r047.002 to r047.016)

 

 

(r047.001, r949.001 or r949.009 with acknowledged error)

 

 

 

 

 

 

 

 

 

 

F029 Motor overtemperature (active in all operating states)

Select via

P493=2 or 3 (temperature sensor at terminals 22 / 23) or

 

P494=2 or 3 (temperature sensor at terminals 204 / 205)

When parameter P490.01=1 (KTY84 at terminals 22 / 23) or P490.02=1 (KTY84 at terminals 204 / 205):

The fault message is activated if the motor temperature reaches or exceeds the value set in parameter P492.

When parameter P490.01=2, 3, 4 or 5 (PTC thermistor at terminals 22 / 23) or P490.02=2, 3, 4 or 5 (PTC thermistor at terminals 204/ 205):

The fault message is activated if the motor temperature reaches or exceeds the response value of the selected PTC thermistor. Fault value:

1Fault activation through temperature sensor at terminals 22 / 23

2Fault activation through temperature sensor at terminals 204 / 205

9.1.2.5Drive faults

NOTICE

The monitoring functions F031, F035, F036, and F037 are deactivated in the delivery state.

They can be activated via parameter P820.

F030 Commutation failure or overcurrent has occurred

(active in operating states of – –, I, II)

Possible error causes

Mains voltage dip in regenerative feedback mode

Current control loop not optimized

Fault value:

r047 Index 002 to 016:

 

 

 

 

1

The blocking voltage time area for the commutating

i002

Delay angle (K0100) in case of error

 

thyristor pair was too small

i003

Actual EMF (K0287) in case of error

 

 

2

The current crest curve breaks upwards

i004

Trigger circuitry diagnostics (K0989) in case of error

 

 

3

The maximum current value was higher than 250% of

i005

Actual field current (K0265) in case of error

 

rated device current

 

i006

Number of pulses (K0105) in case of error

 

 

4A paralleled SIMOREG DC Master has detected a commutation failure or overcurrent

F031 Speed controller monitoring (active in operating states of – –, I, II)

The monitor responds when the difference between the connectors selected in P590 and P591 (factory setting: Setpoint/actual value difference of speed controller) exceeds the limit set in parameter P388 for longer than the time set in parameter P390.

Possible fault causes

Open control loop

Controller not optimized

P590 or P591 is not correctly parameterized

9.1.2.6External faults

F033

Fault message from free function block FB4 (active in all operating states)

Fault value:

1the binector wired via parameter U102 Index.001 is in the state log.”1”

2the binector wired via parameter U102 Index.002 is in the state log.”1”

3the binector wired via parameter U102 Index.003 is in the state log.”1”

4the binector wired via parameter U102 Index.004 is in the state log.”1”

Siemens Energy & Automation

9-9

SIMOREG DC Master Base Drive Panel

Operating Instructions

Page 98
Image 98
Siemens 6RA70 specifications Drive faults, F029 Motor overtemperature active in all operating states