Siemens 6RA70 specifications 10-81, See Change Access / Status P795 Options for G-SST2, P798

Models: 6RA70

1 232
Download 232 pages 59.99 Kb
Page 202
Image 202

PNU

Description

Value range [Unit] Steps

No. indices Factory setting Type

See Change (Access / Status)

P795

Options for G-SST2

(G171)

i001:

0 = Bus terminator OFF

 

1 = Bus terminator ON

(G173)

 

i002: 0 = Bit 10 of the 1st receive word does not function as "Control

 

 

by PLC".

 

 

1 = Bit 10 of the 1st receive word does function as "Control by

 

 

PLC“, i.e. when bit 10 = 0, all other bits of the 1st receive word,

 

 

as well as receive words 2 to 16, are not written to connectors

 

 

K6001 to K6016, or to binectors B6100 to B6915. All these

 

 

connectors and binectors retain their old values.

 

 

P796

USS bus address for G-SST2

*

This parameter is functional only when P790=2 (USS protocol). Address via

(G171)

which the unit can be addressed in USS bus operation.

 

 

 

P797

Telegram failure time for G-SST2

(G171)

The failure time set in this parameter is valid when setting P790=2 (USS

protocol) or P790=5 (peer-to-peer) is selected.

(G173)

 

 

 

0.000

No time monitoring

 

0.001...65.000 Time which may elapse between the receipt of two

 

 

telegrams addressed to the unit before a fault message

 

 

is activated.

 

Fault message F012 is activated if no valid telegram is received within this

 

time period.

Note:

The telegram monitoring function is active

from the receipt of the first error-free telegram after connection of the electronics power supply

from the receipt of the first error-free telegram after the telegram monitor has responded (i.e. monitoring timeout).

Since the telegram transfer time is dependent on the set baud rate, the following minimum setting values for P797 are recommended:

 

Baud rate as set in P793:

Recommended minimum value for P797:

 

300

baud

0.520s

 

600

baud

0.260s

 

1200

baud

0.140s

 

2400

baud

0.080s

 

4800

baud

0.040s

 

Note:

 

 

 

If the "Automatic restart" function is selected (P086>0) on the peer-to-peer

 

communication partner, then only a parameter setting of P797>P086 (on the

 

communication partner) is meaningful.

 

 

 

P798

Source for activation of F012

 

*

Selection of binector which will activate fault message F012 when it

(G171)

switches to log. "1"

 

(G173)

 

 

 

 

 

6030 = binector B6030

 

 

6031 = binector B6031

 

0 to 1

1

0 to 30

1

0.000 to 65.000 [s]

0.001s

6030, 6031

Ind: 2

P052

= 3

FS=0

P051

= 40

Type: O2

Offline

Ind: None

P052

= 3

FS=0

P051

= 40

Type: O2

Offline

 

 

 

Ind: None

P052

= 3

FS=0.000

P051

= 40

Type: O2

Offline

Ind: None

P052

= 3

FS=6030

P051

= 40

Type: L2

Offline

SIEMENS Energy & Automation

10-81

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 202
Image 202