Siemens 6RA70 specifications 10-12

Models: 6RA70

1 232
Download 232 pages 59.99 Kb
Page 133
Image 133

 

PNU

 

Description

 

Value range

 

 

No. indices

 

See

 

 

 

 

 

 

[Unit]

 

 

Factory

 

Change

 

 

 

 

 

 

Steps

 

 

setting

 

(Access /

 

 

 

 

 

 

 

 

 

Type

 

Status)

 

P053

 

Control word for the permanent memory

[SW 1.7 and later]

0 to 1

 

 

Ind: 2

 

P052 = 3

*

 

Disabling or enabling write accesses to the permanent memory

1

 

 

FS=1

 

P051 = 0

 

 

 

 

 

 

Type: O2

 

on-line

 

 

 

 

 

 

 

 

 

 

 

 

 

i001:

Disabling or enabling write accesses to the parameter memory

 

 

 

 

 

 

 

 

 

 

0 Only save parameter P053 in the permanent memory;

 

 

 

 

 

 

 

 

 

 

parameter changes are active immediately but the changed

 

 

 

 

 

 

 

 

 

 

values are only stored temporarily and are lost when the

 

 

 

 

 

 

 

 

 

 

electronics supply voltage is switched off

 

 

 

 

 

 

 

 

 

 

 

1 Save all parameter values in the permanent memory

 

 

 

 

 

 

 

 

 

i002:

Disabling or enabling write accesses to the memory of the

 

 

 

 

 

 

 

 

 

 

nonvolatile process data

 

 

 

 

 

 

 

 

 

 

 

0 Do not save nonvolatile process data in the permanent

 

 

 

 

 

 

 

 

 

 

memory

 

 

 

 

 

 

 

 

 

 

 

1 Save all nonvolatile process data in the permanent memory

 

 

 

 

 

 

 

 

 

 

If the nonvolatile process data are not stored (P053.002=0),

 

 

 

 

 

 

 

 

 

 

data are lost when the electronics supply of the SIMOREG DC

 

 

 

 

 

 

 

 

 

 

Master is switched off, i.e. they have the value 0 after the

 

 

 

 

 

 

 

 

 

 

electronics supply is switched on again:

 

 

 

 

 

 

 

 

 

 

 

K0240: Setpoint of the motor potentiometer

 

 

 

 

 

 

 

 

 

 

 

K0309: Motor heating

 

 

 

 

 

 

 

 

 

 

 

K0310: Thyristor heating

 

 

 

 

 

 

 

 

 

 

 

K9195: Output of the 1st tracking/storage element

 

 

 

 

 

 

 

 

 

 

K9196: Output of the 2nd tracking/storage element

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P054

 

OP1S – Background lighting

 

0, 1

 

 

Ind: None

P052 = 3

 

 

0

ON continuously

 

 

 

FS=0

P051 0

 

 

 

 

 

Type: O2

Online

 

 

1

ON when panel is in use

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P055

 

Copy function data set

 

011 to 143

 

Ind: None

P052 = 3

*

 

This parameter allows parameter set 1, 2, 3 or 4 to be copied to parameter

1

 

FS=012

P051 = 40

 

 

 

 

 

Type: L2

Offline

 

(G175)

 

set 1, 2, 3 or 4. This function is applicable only to parameters with 4 indices

 

 

 

 

 

 

 

 

 

 

 

 

in the function data set (see also Section 9.1, Data sets and Section 9.11,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and Section 8, Sheet G175).

 

 

 

 

 

 

 

 

 

 

0xy

Do nothing, automatic resetting value at the end of a copy

 

 

 

 

 

 

 

 

 

 

operation.

 

 

 

 

 

 

 

 

 

 

1xy

The contents of parameter set x (source data set, x=1, 2, 3 or 4)

 

 

 

 

 

 

 

 

 

 

are copied to parameter set y (target data set, y=1, 2, 3 or 4)

 

 

 

 

 

 

 

 

 

 

(parameter set x remains unchanged, the original contents of

 

 

 

 

 

 

 

 

 

 

parameter set y are overwritten).

 

 

 

 

 

 

 

 

 

 

 

x and y are the respective parameter set numbers (1, 2, 3 or 4)

 

 

 

 

 

 

 

 

 

 

of the source and target parameter sets.

 

 

 

 

 

 

 

 

 

 

The copy operation is started by switching P055 over into parameter mode

 

 

 

 

 

 

 

 

 

when P055=1xy.

 

 

 

 

 

 

 

 

 

 

During the copy operation, the numbers of the parameters being copied are

 

 

 

 

 

 

 

 

 

displayed on the operator panel (PMU).

 

 

 

 

 

 

 

 

 

 

At the end of the copy operation, P055 is reset to P055=0xy.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r056

 

Display of active function data set

 

1 to 4

 

Ind: None

P052 = 3

 

(G175)

 

 

 

 

1

 

Type: O2

 

 

 

P057

 

Copy Bico data set

 

011 to 121

 

Ind: None

P052 = 3

*

 

This parameter allows parameter set 1 or 2 to be copied to parameter set 1

1

 

FS=012

P051 = 40

 

 

 

 

 

Type: L2

Offline

 

 

 

or 2. This function is applicable only to parameters with 2 indices in the Bico

 

 

 

 

 

 

 

 

 

 

 

 

(G175)

 

data set (see also Section 9.1, Data sets and Section 9.11, and Section 8,

 

 

 

 

 

 

 

 

 

Sheet G175).

 

 

 

 

 

 

 

 

 

 

0xy

Do nothing, automatic resetting value at the end of a copy

 

 

 

 

 

 

 

 

 

 

operation.

 

 

 

 

 

 

 

 

 

 

1xy

The contents of parameter set x (source data set, x=1 or 2) are

 

 

 

 

 

 

 

 

 

 

copied to parameter set y (target data set, y=1 or 2) (parameter

 

 

 

 

 

 

 

 

 

 

set x remains unchanged, the original contents of parameter set

 

 

 

 

 

 

 

 

 

 

y are overwritten).

 

 

 

 

 

 

 

 

 

 

 

x and y are the respective parameter set numbers (1 or 2) of the

 

 

 

 

 

 

 

 

 

 

source and target parameter sets.

 

 

 

 

 

 

 

 

 

 

The copy operation is started by switching P057 over into parameter mode

 

 

 

 

 

 

 

 

 

when P057=1xy.

 

 

 

 

 

 

 

 

 

 

During the copy operation, the numbers of the parameters being copied are

 

 

 

 

 

 

 

 

 

displayed on the operator panel (PMU).

 

 

 

 

 

 

 

 

 

 

At the end of the copy operation, P057 is reset to P057=0xy.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r058

 

Display of active Bico data set

 

1 to 2

 

Ind: None

P052 = 3

 

(G175)

 

 

 

 

1

 

Type: O2

 

 

10-12

 

 

 

 

 

SIEMENS Energy & Automation

 

 

 

 

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 133
Image 133
Siemens 6RA70 specifications 10-12