PNU

 

Description

 

 

Value range

 

No. indices

See

 

 

 

 

 

 

[Unit]

 

Factory

Change

 

 

 

 

 

 

Steps

 

setting

(Access /

 

 

 

 

 

 

 

 

Type

Status)

 

P601

 

Source for armature current controller setpoint

 

All connector

Ind: 6

P052 = 3

*

 

i001,i002 Speed limiting controller:

 

numbers

FS=

P051 = 40

 

 

 

 

1

i001: 141

Offline

 

 

 

 

Selection of connectors to be injected as input quantities for

 

(G160)

 

 

 

i002: 0

 

 

(G161)

 

 

the speed limiting controller. Both values are added.

 

i003: 134

 

 

(G162)

 

i003,i004 Current limitation:

 

 

i004: 0

 

 

 

 

 

 

i005: 125

 

 

 

 

 

Selection of connectors to be injected as armature current

 

 

 

 

 

 

 

i006: 0

 

 

 

 

 

controller setpoint (before current limitation). Both values are

 

 

 

 

 

 

 

Type: L2

 

 

 

 

 

added.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i005,i006 Current control:

[SW 1.8 and later]

 

 

 

 

 

 

 

 

Selection of which connectors are connected as the armature

 

 

 

 

 

 

 

 

current controller setpoint (before current controller). The

 

 

 

 

 

 

 

 

two values are added. The magnitude is formed from the

 

 

 

 

 

 

 

 

value selected with index 6.

 

 

 

 

 

 

 

Settings:

 

 

 

 

 

 

 

 

 

0 = connector K0000

 

 

 

 

 

 

 

 

1 = connector K0001

 

 

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P602

 

Source for armature current controller actual value

All connector

Ind: None

P052 = 3

*

 

Selection of connector to be injected as armature current controller

numbers

FS=117

P051 = 40

 

 

 

1

Type: L2

Offline

 

(G162)

 

actual value

 

 

 

 

 

 

 

 

0 = connector K0000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 = connector K0001

 

 

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

P603

 

Source for variable current limit in torque direction I

All connector

 

Ind: 7

P052 = 3

*

 

 

 

 

numbers

 

FS=

P051 = 40

 

 

 

 

 

 

1

 

i001: 1

Offline

 

(G161)

 

i001..i004Selection of connector to be injected as variable current limit

 

 

i002: 1

 

 

 

 

 

i003: 1

 

 

 

 

in torque direction I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

i004: 1

 

 

 

 

 

Normalization: +100% corresponds to P100*P171

 

 

 

 

 

 

 

 

 

i005: 1

 

 

 

 

 

 

 

 

 

 

 

 

 

i005

Selection of connector to be injected as current limit in torque

 

 

i006: 2

 

 

 

 

 

direction I with Fast Stop or Shutdown

 

 

 

i007: 2

 

 

 

 

 

Normalization: +100% corresponds to P100*P171

 

 

Type: L2

 

 

 

 

i006

Selection of connector to be injected as variable current limit

 

 

 

 

 

 

 

 

in torque direction I

 

 

 

 

 

 

 

 

 

Normalization: +100% corresponds to r072.002

 

 

 

 

 

 

 

 

[can be set in SW 1.9 and later]

 

 

 

 

 

 

 

 

i007

Selection of connector to be injected as current limit in torque

 

 

 

 

 

 

 

 

direction I with Emergency Stop or Shutdown

 

 

 

 

 

 

 

 

Normalization: +100% corresponds to r072.002

 

 

 

 

 

 

 

 

[can be set in SW 1.9 and later]

 

 

 

 

 

Settings:

0 = connector K0000

1 = connector K0001 etc.

10-60

SIEMENS Energy & Automation

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 181
Image 181