Siemens Energy & SIMOREG DC Master

12

3

4

5

6

6RA70 DC MASTER

SIMPLIFIED BLOCK DIAGRAM

(ALL AVAILABLE FUNCTIONS ARE NOT SHOWN ON SIMPLIFIED BLOCK DIAGRAM)

78

Sheet 12

Automation Base Drive Panel Operating Instructions

11-13

Status word 1

Bit No.

from sequencing control

Bit 0

from sequencing control

Bit 1

 

from sequencing control

Bit 2

 

from fault processing

Bit 3

 

rom sequencing control

Bit 4

 

from sequencing control

Bit 5

 

from sequencing control

Bit 6

 

from alarm processing

Bit 7

from sheet "Signals"

Bit 8

 

from sequencing control

Bit 9

 

from sheet "Signals"

Bit 10

 

from fault processing

Bit 11

from sequencing control

Bit 12

from setpoint processing

Bit 13

(part 2)

 

from sheet "Signals"

Bit 14

 

Bit 15

Meaning

1 = Ready to switch on

0 = Not ready to switch on

1 = Ready to operate (pulses disabled)

0 = Not ready to operate

1 = Run (output terminals energized)

0 = Pulses disabled

1 = Fault is active (pulses disabled)

0 = No fault is active

0 = OFF2 applied

1 = No OFF2 applied

0 = OFF3 applied

1 = No OFF3 applied

1 = Switch-on inhibit

0 = No switch-on inhibit (converter can be switched on)

1 = Alarm is active

0 = No alarm is active

0 = Setpoint/actual value deviation detected

1 = No setpoint/actual value deviation detected

1 = PZD control requests (always 1)

1 = Comparison setpoint reached

0 = Comparison setpoint not reached

1 = Undervoltage fault

0 = No undervoltage fault is active

1 = Request to energize main contactor

0 = Request not to energize main contactor

1 = Ramp-function generator active

0= Ramp-function generator not active

1= Positive speed setpoint

0 = Negative speed setpoint

Spare

r652

Status word 1

K0032

 

B0100

 

1

B0101

B0102

 

1

B0103

B0104

 

1

B0105

B0106

 

1

B0107

B0108

 

1

B0109

B0110

 

1

B0111

B0112

 

1

B0113

B0114

 

1

B0115

B0116

 

1

B0117

B0120

 

1

B0121

B0122

 

1

B0123

B0124

 

1

B0125

B0126

 

1

B0127

B0128

 

1

B0129

15 14 13 12 11 10 9 Bit8

7 6 5 4 3 2 1 Bit0

Display of status word 1 (r652)

on 7-segment display

12

Status Word 1

Page 228
Image 228
Siemens 6RA70 specifications Status Word, Status word