Alarm

 

Description

 

 

 

 

No.

 

 

 

 

 

 

 

A025

Brush length too short

 

(active in all operating states)

 

When parameter P495=1 (binary sensing of brush length):

 

Alarm in response to log. “0” signal (longer than 10s) at terminal 211

Possible causes

Encoder for brush length has responded

Interruption in encoder cable

A026 Poor bearing condition (active in all operating states)

When parameter P496=1 (bearing condition sensing):

Alarm in response to log. “0” signal (longer than 2s) at terminal 212

Possible causes

Encoder for bearing condition has responded

A027 Air flow monitoring

(active in operating states of < o6)

When parameter P497=1 (air flow monitoring):

Alarm in response to log. “0” signal (longer than 40s) at terminal 213

Possible causes

Encoder for fan monitoring has responded

Interruption in encoder cable

A028 Motor overtemperature (active in all operating states)

When parameter P498=1 (thermostat connected):

Alarm in response to log. “0” signal (longer than 10s) at terminal 214

Possible causes

Thermostat for monitoring motor temperature has responded

Interruption in encoder cable

A029 Motor overtemperature (active in all operating states)

Selection via P493=1 or 3 (thermostat at terminals 22 / 23) or

P494=1 or 3 (thermostat at terminals 204 / 205)

When parameter P490.01=1 (KTY84 at terminals 22 / 23) or P490.02=1 (KTY84 at terminals 204 / 205):

The alarm is activated if the motor temperature reaches or exceeds the values set in parameter P492.

When parameter P490.01=2, 3, 4 or 5 (PTC thermistor at terminals 22 / 23) or P490.02=2, 3, 4 or 5 (PTC thermistor at terminals

204 / 205):

The alarm is activated if the motor temperature reaches or exceeds the trip value of the selected PTC.

A030 Commutation failure or overcurrent has occurred

(active in operating states of – –, I, II)

Possible error causes

Mains voltage dip in regenerative feedback mode

Current control loop not optimized

A031 Speed controller monitoring (active in operating states of – –, I, II)

The monitor responds when the difference between the connectors selected in P590 and P591 (factory setting: Setpoint/actual value difference of speed controller) exceeds the limit set in parameter P388 for longer than the time set in parameter P390.

Possible causes

Control loop interrupted

Controller is not optimized

P590 or P591 is not correctly parameterized

Siemens Energy & Automation

9-29

SIMOREG DC Master Base Drive Panel

Operating Instructions

Page 118