Siemens 6RA70 specifications Closed-loop EMF control, 10-38

Models: 6RA70

1 232
Download 232 pages 59.99 Kb
Page 159
Image 159

PNU

Description

Value range

No. indices

See

 

 

[Unit]

Factory

Change

 

 

Steps

setting

(Access /

 

 

 

Type

Status)

10.13 Closed-loop EMF control

P272

Operating mode of closed-loop EMF control

 

0 to 1

 

Ind: None

P052

= 3

*

0

Fault message F043 (”EMF too high for braking operation") is

1

 

FS=0

P051

= 40

 

 

 

Type: O2

Offline

(G165)

 

active: If the EMF is too high when a torque direction change is

 

 

 

 

 

 

 

 

 

 

requested (i.e. if the calculated firing angle (K0101) for the

 

 

 

 

 

 

 

armature current in the new torque direction is > 165 degrees),

 

 

 

 

 

 

 

both torque directions are disabled. If, at the same time, the

 

 

 

 

 

 

 

absolute value of the armature current required in the new

 

 

 

 

 

 

 

torque direction is > 0.5% of rated converter DC current (P072),

 

 

 

 

 

 

 

fault message F043 is activated (see Section 10 for possible

 

 

 

 

 

 

 

fault causes).

 

 

 

 

 

 

 

1

Alarm A043 and automatic field reduction if EMF is too high in

 

 

 

 

 

 

 

braking operation.

 

 

 

 

 

 

 

 

If the EMF is too high in braking operation (i.e. if the following

 

 

 

 

 

 

 

applies to the armature firing angle α before limitation (K0101):

 

 

 

 

 

 

 

α > (αW – 5 degrees)), alarm A043 is activated (αW is the

 

 

 

 

 

 

 

inverter stability limit according to P151 or 165 degrees with a

 

 

 

 

 

 

 

discontinuous armature current).

 

 

 

 

 

 

 

 

The field is reduced with activation of A043. This field reduction

 

 

 

 

 

 

 

is achieved by regulating the armature firing angle to (αW – 5

 

 

 

 

 

 

 

degrees) by means of a P controller, whose output reduces the

 

 

 

 

 

 

 

EMF controller setpoint. "Field weakening operation by internal

 

 

 

 

 

 

 

closed-loop EMF control" (P081=1) must therefore be

 

 

 

 

 

 

 

parameterized so that the field reduction can take effect.

 

 

 

 

 

 

 

When a torque direction change is requested, both torque

 

 

 

 

 

 

 

directions remain disabled until the field, and thus the EMF,

 

 

 

 

 

 

 

have been reduced accordingly (i.e. until the calculated firing

 

 

 

 

 

 

 

angle (K0101) for the armature current required in the new

 

 

 

 

 

 

 

torque direction is <165 degrees).

 

 

 

 

 

 

P273

Control word for EMF controller precontrol

 

0 to 1

 

Ind: 4

P052

= 3

*

0

EMF controller precontrol disabled, precontrol output = rated

1

 

FS=1

P051

= 40

FDS

 

 

Type: O2

Offline

 

motor field current (P102)

 

 

 

(G165)

 

 

 

 

 

 

 

1

EMF controller precontrol is active

 

 

 

 

 

 

 

 

 

 

 

 

 

P274

Set EMF controller I component to zero

 

0 to 1

 

Ind: 4

P052

= 3

*

0

Set controller I component to zero (i.e. to obtain pure P

1

 

FS=1

P051

= 40

FDS

 

 

Type: O2

Offline

 

controller)

 

 

 

(G165)

 

 

 

 

 

 

 

1

Controller I component is active

 

 

 

 

 

 

 

 

 

 

 

 

 

P275

EMF controller P gain

 

0.10 to 100.00

 

Ind: 4

P052

= 3

*

This parameter is automatically set during the field weakening optimization

0.01

 

FS=0.60

P051

= 40

FDS

 

 

Type: O2

Online

run (P051=27).

 

 

 

(G165)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P276

EMF controller reset time

 

0.010 to 10.000

 

Ind: 4

P052

= 3

*

This parameter is automatically set during the field weakening optimization

[s]

 

FS=0.200

P051

= 40

FDS

0.001s

 

Type: O2

Online

run (P051=27).

 

 

(G165)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P277

EMF controller droop

 

0.0 to 10.0

 

Ind: 4

P052

= 3

*

 

 

 

[%]

 

FS=0.0

P051

= 40

FDS

 

 

 

0.1%

 

Type: O2

Online

(G165)

 

 

 

 

 

 

 

 

P280

Filter time for setpoint for EMF controller precontrol

[SW 1.9 and later]

0 to 10000

 

Ind: 4

P052

= 3

 

Filtering of the EMF setpoint at the input of the EMF controller precontrol.

[ms]

 

FS=0

P051

= 40

FDS

1ms

 

Type: O2

on-line

The purpose of this filter is to decouple the EMF controller precontrol from

 

(G165)

 

 

 

 

 

the EMF controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P281

Filter time for setpoint for EMF controller

[SW 1.9 and later]

0 to 10000

 

Ind: 4

P052

= 3

 

Filtering of the EMF setpoint at the input of the EMF controller.

[ms]

 

FS=0

P051

= 40

FDS

1ms

 

Type: O2

on-line

The purpose of this filter is to decouple the EMF controller precontrol from

 

(G165)

 

 

 

 

 

the EMF controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P282

Filter time for actual value for EMF controller

[SW 1.9 and later]

0 to 10000

 

Ind: 4

P052

= 3

FDS

Filtering of actual EMF value at the input of the EMF controller.

[ms]

 

FS=0

P051

= 40

1ms

 

Type: O2

on-line

(G165)

 

 

 

 

 

 

 

 

 

 

 

 

P283

Filter time for actual value for EMF controller precontrol

0 to 10000

 

Ind: 4

P052

= 3

 

 

 

[SW 1.9 and later]

[ms]

 

FS=0

P051

= 40

FDS

Filtering of actual speed value at the input of the EMF controller precontrol.

1ms

 

Type: O2

on-line

(G165)

 

 

 

 

 

The purpose of this filter is to stabilize the EMF controller precontrol, even

 

 

 

 

 

 

 

 

 

 

 

 

when the actual speed signal is unsteady or distorted by harmonics.

 

 

 

 

 

 

 

 

 

 

 

 

 

10-38

 

 

 

 

SIEMENS Energy & Automation

 

 

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 159
Image 159
Siemens 6RA70 specifications Closed-loop EMF control, 10-38