Siemens 6RA70 specifications 10-56, Speed controller adaptation, P550 Gain in the adaptation range

Models: 6RA70

1 232
Download 232 pages 59.99 Kb
Page 177
Image 177

PNU

Description

Value range

No. indices

See

 

 

[Unit]

Factory

Change

 

 

Steps

setting

(Access /

 

 

 

Type

Status)

10.31 Speed controller

(see also Section 8, Sheet G151 of Operating Instructions 6RX1700-0AD**)

further parameters for the speed controller P200 - P236

Speed controller adaptation

The parameters of the speed controller (Kp, Tn, droop) can be altered as a function of any connector to adapt the speed controller optimally to a changing controlled system.

The diagrams below show the active P gain, the active Integration time and the active droop depending on the value of the set connector.

Adaptation of the P gain:

 

KP

 

 

 

 

 

 

 

P550

 

 

 

 

 

 

 

P225

 

 

 

 

 

 

 

Threshold 1

Threshold 2

Input

 

 

 

 

 

P556

P559

selected in P553

 

 

 

 

Adaptation of the integration time:

 

 

 

 

 

 

 

Tn

 

 

 

 

 

 

 

P551

 

 

 

 

 

 

 

P226

 

 

 

 

 

 

 

Threshold 1

Threshold 2

Input

 

 

 

 

 

P557

P560

selected in P554

 

 

 

 

Adaptation of the droop:

 

 

 

 

 

 

 

St

 

 

 

 

 

 

 

P552

 

 

 

 

 

 

 

P227

 

 

 

 

 

 

 

Threshold 1

Threshold 2

Input

 

 

 

 

 

P558

P561

selected in P555

 

 

 

 

For parameter pairs P225/P550, P226/P551 and P227/P552 all values can be set completely mutually independently, e.g., P550 does not

have to be greater than P225. The above diagrams show only the effect of the individual parameters.

 

 

 

Threshold 1 must always be set smaller than threshold 2, otherwise the fault message F058 is activated.

 

 

 

P550

P gain in the adaptation range

 

 

0.10 to 200.00

 

Ind: 4

P052 = 3

FDS

Value of Kp, if Influencing quantity Threshold 1

 

0.01

 

FS=3.00

P051 = 40

(G151)

 

 

 

Type: O2

on-line

P551

Integration time in the adaptation range

 

[SW 1.7 and later]

0.010 to 10.000

 

Ind: 4

P052 = 3

FDS

Value of Tn, if Influencing quantity Threshold 1

 

[s]

 

FS=0.650

P051 = 40

(G151)

 

0.001s

 

Type: O2

on-line

P552

Droop in the adaptation range

 

[SW 1.7 and later]

0.0 to 10.0

 

Ind: 4

P052 = 3

FDS

Value of droop, if Influencing quantity Threshold 1

 

[%]

 

FS=0.0

P051 = 40

(G151)

 

0.1%

 

Type: O2

on-line

P553

Source for the Influencing quantity of the Kp adaptation

All connector

 

Ind: 4

P052 = 3

*

Selection of which connector is connected at the influencing quantity for

numbers

 

FS=0

P051 = 40

FDS

1

 

Type: L2

off-line

adaptation of the n controllers P gain

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(G151)

0 = connector K0000

 

 

 

 

 

 

 

1 = connector K0001

 

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

 

P554

Source for the Influencing quantity of the Tn-adaptation

All connector

 

Ind: 4

P052 = 3

*

 

 

[SW 1.7 and later]

numbers

 

FS=0

P051 = 40

FDS

Selection of which connector is connected at the influencing quantity for

1

 

Type: L2

off-line

 

 

 

 

(G151)

adaptation of the n controllers integration time

 

 

 

 

 

0 = connector K0000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 = connector K0001

 

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10-56

 

 

 

 

SIEMENS Energy & Automation

 

 

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 177
Image 177
Siemens 6RA70 10-56, Speed controller adaptation, P550 Gain in the adaptation range, P552 Droop in the adaptation range