PNU

 

Description

 

Value range

 

No. indices

 

See

 

 

 

 

 

 

 

 

[Unit]

 

Factory

 

Change

 

 

 

 

 

 

 

Steps

 

setting

 

(Access /

 

 

 

 

 

 

 

 

 

Type

 

Status)

 

P464

 

Time difference for dy/dt

 

0.01 to 300.00

 

Ind: 4

 

P052

= 3

 

 

 

Setting of dt for the output of dy/dt at a connector,

 

[s]

 

FS=10.00

 

P051

= 40

 

FDS

 

 

0.01s

 

Type: O2

 

Online

 

 

i.e. on K0241 the change in the output quantity (K0240) is output within the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(G126)

 

time set in P464, multiplied by the factor set in P465

 

 

 

 

 

 

 

 

 

(unit of time setting is [s] if P465=0 or [min] if P465=1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example: -

The ramp-function generator is currently ramping up with a

 

 

 

 

 

 

 

 

 

 

 

 

ramp-up time of P462=5s, i.e. a ramp-up operation from y=0%

 

 

 

 

 

 

 

 

 

 

 

 

to y=100% takes 5s.

 

 

 

 

 

 

 

 

 

 

 

-

A time difference dt of P464=2s is set.

 

 

 

 

 

 

 

 

 

 

 

- A dy/dt of 40% appears at connector K0241 since the dy

 

 

 

 

 

 

 

 

 

 

 

 

within the set dt of 2 s equals (2s/5s)*100%.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P465

 

Factor of expansion for motorized potentiometer

 

0 to 1

 

Ind: 4

 

P052

= 3

*

 

The effective ramp-up time, ramp-down time or time difference for dy/dt is

1

 

FS=0

 

P051

= 40

 

FDS

 

 

 

 

Type: O2

 

Online

 

 

the product of the time setting in parameter P462, P463 and P464

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(G126)

 

respectively, multiplied by the factor set in this parameter.

 

 

 

 

 

 

 

 

0

Parameters P462, P463 and P464 are multiplied by a factor of 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Parameters P462, P463 and P464 are multiplied by a factor of 60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P466

 

Source for motorized potentiometer setting value

 

All connector

 

Ind: 4

 

P052

= 3

*

 

Selection of the connector to be injected as the motorized potentiometer

 

numbers

 

FS=0

 

P051

= 40

 

FDS

 

1

 

Type: L2

 

Offline

 

 

setting value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(G126)

 

0 = connector K0000

 

 

 

 

 

 

 

 

 

 

1 = connector K0001

 

 

 

 

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P467

 

Motorized potentiometer starting value

 

-199.9 to 199.9

Ind: 4

P052

= 3

 

FDS

 

Starting value of motorized potentiometer after ON when P473 = 0

[%]

FS=0.0

P051

= 40

 

(G126)

 

0.1%

Type: I2

Online

 

 

 

 

 

 

P468

 

Setpoint for "Raise motorized potentiometer”

 

-199.99 to 199.99

Ind: 4

P052

= 3

 

FDS

 

Motorized potentiometer manual operation: Setpoint for "Raise motorized

[%]

FS=100.00

P051

= 40

 

(G126)

 

0.01%

Type: I2

Online

 

 

potentiometer"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P469

 

Setpoint for "Lower motorized potentiometer ”

 

-199.99 to 199.99

Ind: 4

P052

= 3

 

FDS

 

Motorized potentiometer manual operation: Setpoint for "Lower motorized

[%]

FS=-100.00

P051

= 40

 

(G126)

 

0.01%

Type: I2

Online

 

 

potentiometer"

 

 

 

 

 

 

 

 

 

 

 

P470

 

Source for clockwise/counter-clockwise switchover

 

All binector numbers

Ind: 2

P052

= 3

*

 

Selection of binector to control "Clockwise/counter-clockwise

1

FS=0

P051

= 40

 

BDS

 

 

 

Type: L2

Offline

 

 

switchover"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(G126)

 

("0" state = clockwise).

 

 

 

 

 

 

 

 

 

0 = binector B0000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 = binector B0001

 

 

 

 

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P471

 

Source for manual/automatic switchover

 

All binector numbers

 

Ind: 2

 

P052

= 3

*

 

Selection of binector to control "Manual/automatic switchover"

1

 

FS=0

 

P051

= 40

 

BDS

 

 

 

 

Type: L2

 

Offline

 

 

("0" state = manual).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(G126)

 

0 = binector B0000

 

 

 

 

 

 

 

 

 

 

1 = binector B0001

 

 

 

 

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P472

 

Source for set motorized potentiometer

 

All binector numbers

Ind: 2

P052

= 3

*

 

Selection of binector to control "Set motorized potentiometer"

1

FS=0

P051

= 40

 

BDS

 

 

 

Type: L2

Offline

 

 

("0" to "1" transition = set motorized potentiometer).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(G126)

 

0 = binector B0000

 

 

 

 

 

 

 

 

 

 

1 = binector B0001

 

 

 

 

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P473

 

Storage of output value

 

0 to 1

 

Ind: 4

P052

= 3

*

0

 

No storage of output value:

1

 

FS=0

P051

= 40

 

FDS

 

 

 

 

Type: O2

Offline

 

 

 

 

The output is set to 0 in all operating states of >o5.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(G126)

 

 

 

The starting point after ON is determined by P467 (MOP starting

 

 

 

 

 

 

 

 

 

 

 

value).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

Non-volatile storage of output value:

 

 

 

 

 

 

 

 

 

 

 

 

The output value remains stored in all operating states and after

 

 

 

 

 

 

 

 

 

 

 

 

voltage disconnection or failure. The last value stored is output

 

 

 

 

 

 

 

 

 

 

 

 

again after voltage recovery/reconnection.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 