See Change (Access / Status)

P360

Response delay for external faults and alarms

 

(G180)

The fault message or alarm is not activated on the converter until the

appropriate input or corresponding control word bit (as selected in P675,

(G181)

P686, P688 or P689) has been in the LOW state for at least the time period

 

 

set in this parameter (see also Section 8, Sheets G180 and G181).

 

i001:

Delay for external fault 1

 

 

i002:

Delay for external fault 2

 

 

i003:

Delay for external alarm 1

 

 

i004:

Delay for external alarm 2

 

 

 

 

P361

Delay time for the undervoltage monitoring

[SW 1.7 and later]

FDS

Activation of the fault message F006 (line undervoltage) is delayed by the

 

time that can be set in this parameter. During this delay time firing pulses

 

are output!

 

 

 

Another time which is parameterized for automatic restarting (P086) only

 

begins after the time set here has elapsed.

 

 

 

 

P362

Delay time for the overvoltage monitoring

[SW 1.7 and later]

FDS

Activation of the fault message F007 (line overvoltage) is delayed by the

 

time that can be set in this parameter. During this delay time firing pulses

 

are output!

 

 

 

Another time which is parameterized for automatic restarting (P086) only

 

begins after the time set here has elapsed.

 

 

 

 

P363

Threshold for the minimum line frequency

[SW 1.8 and later]

FDS

If the line frequency falls below the value set here and does not rise above it

again within the "restart" time set in P086, the fault message F008 is

 

 

activated. As long as the line frequency is below the value set here, the

 

drive is kept in operating state o4 or o5.

 

 

[values < 45.0 Hz can be set in SW 1.9 and later]

 

CAUTION

Operation in the extended frequency range between 23 Hz and 110 Hz is available on request.

P364

Threshold for the maximum line frequency

[SW 1.8 and later]

FDS

If the line frequency rises above the value set here and does not fall below it

again within the "restart" time set in P086, the fault message F009 is

 

 

activated. As long as the line frequency is above the value set here, the

 

drive is kept in operating state o4 or o5.

 

CAUTION

Operation in the extended frequency range between 23 Hz and 110 Hz is available on request.

0 to 10000 [ms] 1ms

0 to 60000 [ms] 1ms

0 to 60000 [ms] 1ms

23.0to 60.0

[Hz]

0.1Hz

50.0to 110.0

[Hz]

0.1Hz

Ind: 4

P052

= 3

FS=0

P051

= 40

Type: O2

Online

Ind: 4

P052

= 3

FS=0

P051

= 40

Type: O2

on-line

 

 

 

Ind: 4

P052

= 3

FS=10000

P051

= 40

Type: O2

on-line

 

 

 

Ind: 4

P052

= 3

FS=45.0

P051

= 40

Type: O2

on-line

Ind: 4

P052

= 3

FS=65.0

P051

= 40

Type: O2

on-line

10.18 Setting values for limit-value monitors

(see also Section 8, Sheet G187 and G188 of Operating Instructions 6RX1700-0AD**)

n < nmin signal

P370

Speed threshold nmin

FDS

Speed threshold for n < nmin limit-value monitor.

(G187)

Note:

This threshold also affects the sequence of control operations for

 

 

"Shutdown", "Fast stop", cancellation of the "Inching" or "Crawling"

 

command, the "Braking with field reversal" function and the brake control

 

operation (see Section 9).

P371

Hysteresis for n < nmin signal

FDS

This value is added to the response threshold if n < nmin is active.

(G187)

 

0.00to 199.99

[%]

0.01% of maximum speed

0.00to 199.99

[%]

0.01% of maximum speed

Ind: 4

P052

= 3

FS=0,50

P051

= 40

Type: O2

Online

Ind: 4

P052

= 3

FS=0,50

P051

= 40

Type: O2

Online

n < ncomp. signal

SIEMENS Energy & Automation

10-43

SIMOREG DC Master Base Drive Panel Operating Instructions

 