PNU

Description

Value range [Unit] Steps

No. indices Factory setting Type

See Change (Access / Status)

P634

Source for limitation input at ramp-function generator output

*

Selection of connectors which must be added up to provide the limitation

 

(G137)

input at the ramp-function generator output (setpoint limitation).

 

0 = connector K0000

 

1 = connector K0001

 

etc.

 

 

P635

Source for ramp-function generator setpoint

*

Selection of connector to be injected as the ramp-function generator

FDS

setpoint

 

(G135)

0 = connector K0000

 

1 = connector K0001

 

etc.

 

 

P636

Source for reduction signal for ramp-function generator times

*

Selection of connector to be injected as the reduction signal for the ramp-

 

(G136)

function generator times

 

i001 acts on ramp-up and ramp-down time (P303, P304)

 

i002 acts on lower and upper transition roundings (P305, P306)

 

i003 acts on ramp-up time (P303)

 

i004 acts on ramp-down time (P304)

 

i005 acts on lower transition rounding (P305)

 

i006 acts on upper transition rounding (P306)

 

0 = connector K0000

 

1 = connector K0001

 

etc.

All connector numbers

1

All connector numbers

1

All connector numbers

1

Ind: 2

P052

= 3

FS=

P051

= 40

i001: 190

Offline

i002: 0

 

 

Type: L2

 

 

 

 

 

Ind: 4

P052

= 3

FS=194

P051

= 40

Type: L2

Offline

Ind: 6

P052

= 3

FS=1

P051

= 40

Type: L2

Offline

P637

Source for selection of "Ramp-function generator setting 2"

*

Selection of binector to control switchover to "Ramp-function generator

BDS

setting 2".

 

(G136)

With a log. "1" signal at the binector, ramp-function generator parameter set

2 (P307 - P310) is selected. This function has a higher priority than the

 

 

ramp-up integrator function.

 

0 = binector B0000

 

1 = binector B0001

 

etc.

 

 

P638

Source for selection of "Ramp-function generator setting 3”

*

Selection of binector to control switchover to "Ramp-function generator

BDS

setting 3".

 

(G136)

With a log. "1" signal at the binector, ramp-function generator parameter set

3 (P311 - P314) is selected. This function has a higher priority than the

 

 

ramp-up integrator function.

 

0 = binector B0000

 

1 = binector B0001

 

etc.

 

 

P639

Source for the ramp-function generator setting values

*

Selection of the connectors that are connected as the ramp-function

 

(G136)

generator setting values.

 

i001 Setting value for the ramp-function generator output in state log.

 

"1" of the binector selected via P640

 

i002 Setting value for the ramp-function generator output if the drive

 

is not in state "Operating" (B0104=0) and the binector selected

 

via P640 is in state log. "0"

 

[i002 only available with SW 1.6 and later]

 

0 = Connector K0000

 

1 = Connector K0001

 

etc.

 

 

P640

Source for selection of "Set ramp-function generator”

*

Selection of binector to control the "Set ramp-function generator" function

BDS

0 = binector B0000

 

(G136)

1 = binector B0001

 

etc.

All binector numbers

Ind: 2

P052

= 3

1

FS=0

P051

= 40

 

Type: L2

Offline

All binector numbers

Ind: 2

P052

= 3

1

FS=0

P051

= 40

 

Type: L2

Offline

All connector

Ind: 2

P052

= 3

numbers

FS=167

P051

= 40

1

Type: L2

off-line

All binector numbers

Ind: 2

P052

= 3

1

FS=0

P051

= 40

 

Type: L2

Offline

SIEMENS Energy & Automation

10-65

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 186
Image 186
Siemens 6RA70 specifications 10-65