Siemens 6RA70 Further configuring measures, 10-70, P690 Source for control word 2, bit30

Models: 6RA70

1 232
Download 232 pages 59.99 Kb
Page 191
Image 191

 

PNU

 

Description

 

Value range

 

No. indices

 

See

 

 

 

 

 

[Unit]

 

Factory

 

Change

 

 

 

 

 

Steps

 

setting

 

(Access /

 

 

 

 

 

 

 

Type

 

Status)

 

P689

 

Source for control word 2, bit29

 

All binector numbers

Ind: 2

P052 = 3

*

 

(0=external alarm 2, 1=no external alarm 2)

 

1

FS=1

P051 = 40

 

BDS

 

 

 

Type: L2

Offline

 

 

 

 

 

 

(G181)

 

 

 

 

 

 

 

 

 

P690

 

Source for control word 2, bit30

 

All binector numbers

Ind: None

P052 = 3

*

 

(0=select Bico data set 1, 1=select Bico data set 2)

 

1

FS=0

P051 = 40

 

(G181)

 

 

 

Type: L2

Offline

 

 

 

 

 

 

P691

 

Source for control word 2, Bit31

[SW 1.8 and later]

All binector numbers

 

Ind: 2

 

P052 = 3

*

 

Main contactor checkback signal:

 

1

 

FS=0

 

P051 = 40

 

BDS

 

 

 

 

Type: L2

 

Offline

 

 

(0 = main contactor dropped out, 1 = main contactor picked up)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(G181)

 

This control input is intended as a means of looping an auxiliary contact of

 

 

 

 

 

 

 

 

the main contactor into the device control.

 

 

 

 

 

 

 

 

 

During the Power ON routine, this signal must switch to "1" within the time

 

 

 

 

 

 

 

 

period set in P095. If it does not, or it disappears during operation, fault

 

 

 

 

 

 

 

 

message F004 with fault value 6 is activated.

 

 

 

 

 

 

 

 

 

P691 = 0: Bit 31 of control word 2 is inoperative.

 

 

 

 

 

 

 

 

 

(This setting of P691 is always active, regardless of whether

 

 

 

 

 

 

 

 

control word 2 is input in word mode [P649 = 9] or bit mode

 

 

 

 

 

 

 

 

[P649 <> 9])

 

 

 

 

 

 

 

 

 

P691 = 1: Bit 31 of control word 2 is inoperative.

 

 

 

 

 

 

 

 

 

(This setting of P691 is active only when control word 2 is input

 

 

 

 

 

 

 

 

in bit mode, i.e. when P649 <> 9)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.36 Further configuring measures

P692

Source for selection of injection of standstill field

All binector numbers

Ind: 2

P052

= 3

*

Selection of binector to control injection of the standstill field ("0" state =

1

FS=0

P051

= 40

BDS

 

Type: L2

Offline

inject standstill field)

 

 

 

 

 

 

 

 

 

(G166)

Note:

The delay time set in P258 is not effective when this function is

 

 

 

 

 

 

active.

 

 

 

 

 

0 = binector B0000

 

 

 

 

 

1 = binector B0001

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

P693

Source for selection of enabling command for EMF controller

All binector numbers

Ind: 2

P052

= 3

*

Selection of binector which is to control enabling of the EMF controller

1

FS=1

P051

= 40

BDS

 

Type: L2

Offline

0 = binector B0000

 

 

 

 

(G165)

 

 

 

 

1 = binector B0001

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

P694

Source for selection of enabling command for "Torque limit

All binector numbers

Ind: 2

P052

= 3

*

switchover”

1

FS=0

P051

= 40

BDS

Selection of binector which is to control enabling of the "Torque limit

 

Type: L2

Offline

 

 

 

 

(G160)

switchover" function (1=enable, see also Sheet G160 in Section 8 of

 

 

 

 

Operating Instructions 6RX1700-0AD** and P180 to P183)

 

 

 

 

 

 

 

 

 

 

0 = binector B0000

 

 

 

 

 

1 = binector B0001

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

P695

Source for selection of "Set speed controller I component" function

All binector numbers

Ind: 2

P052

= 3

*

Selection of binector to control the "Set I component" function

1

FS=0

P051

= 40

BDS

 

Type: L2

Offline

 

 

 

0 = binector B0000

 

 

 

 

 

 

 

 

 

(G152)

1 = binector B0001

 

 

 

 

 

etc.

 

 

 

 

 

When the binector selected in P695 switches from log. "0" to log. "1", the I component of the speed controller is set to the value of the connector selected in P631.

With this function it is possible, for example, to use the same signal (binector) to control controller enabling commands and setting of the I component.

10-70

SIEMENS Energy & Automation

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 191
Image 191