PNU

Description

Value range [Unit] Steps

No. indices Factory setting Type

See Change (Access / Status)

r959

Alarm parameter 7

 

 

 

 

 

 

 

 

Parameter alarms 7 (TB alarms 1)

 

 

 

 

 

 

If one of the alarms between 97 and 112 is generated, the corresponding

 

segment in the display lights up.

 

 

 

 

 

 

112

111

110

109

108

107

106

105

 

104

103

102

101

100

99

98

97

r960

Alarm parameter 8

 

 

 

 

 

 

 

 

Parameter alarms 8 (TB alarms 2)

 

 

 

 

 

 

If one of the alarms between 113 and 128 is generated, the corresponding

 

segment in the display lights up.

 

 

 

 

 

 

128

127

126

125

124

123

122

121

 

120

119

118

117

116

115

114

113

Ind: None

P052 = 3

Type: V2

 

Ind: None

P052 = 3

Type: V2

 

10.48 Device identification

r964 Parameters for device identification on the PROFIBUS

[SW 2.0 and later]

Display parameters to support overview and diagnosis of all nodes on the PROFIBUS-DP during and after commissioning

(coding according to PROFIBUS profile V3)

i001: Display of the manufacturer of the SIMOREG DC Master 6RA70 : SIEMENS = 42

i002: Display of device type: SIMOREG DC Master 6RA70 = 4110

i003: Display of the software version of the SIMOREG DC Master 6RA70

(see r060.001)

i004: Display of year of generation of the software of the SIMOREG DC Master 6RA70: y y y y

(see r061.001)

i005: Display of the month and day of generation of the software of the SIMOREG DC Master 6RA70: d d m m

(see r061.003 and r061.002)

i006: Display of the controlled axes of the SIMOREG DC Master 6RA70: 1

0 to 65535

1

Ind: 6

Type: O2

P052 = 1

10.49 Visualization parameters: Control and status word

r967

Display of control word 1

 

Visualization parameter for control word 1 (bits 0-15)

 

Identical to r650 (control word 1)

 

 

r968

Display of status word 1

 

Visualization parameter for status word 1 (bits 0 - 15)

 

Identical to r652 (status word 1)

 

 

Ind: None

P052 = 3

Type: V2

 

 

 

Ind: None

P052 = 3

Type: V2

 

 

 

10.50 Resetting and storing parameters,

list of existing and modified P and r parameters

P970 Restore factory setting

*

Reset parameters to factory setting (default)

0:Parameter reset: All parameters are reset to their original values (factory setting). This parameter is then automatically reset to 1.

1:No parameter reset

Note: Function can also be selected by setting P051=21.

0 to 1

1

Ind: None

FS=1

Type: O2

P052 = 3

P051 = 40 Offline

SIEMENS Energy & Automation

10-91

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 212
Image 212
Siemens 6RA70 specifications Device identification, Visualization parameters Control and status word, 10-91