PNU

Description

Value range [Unit] Steps

No. indices Factory setting Type

See Change (Access / Status)

10.39 Binary outputs

(see also Section 8, Sheet G112 of Operating Instructions 6RX1700-0AD**)

P770

Control word for binary selectable outputs

*

i001: 0

Binary selectable output at terminal 46 is not inverted

 

(G112)

1

Binary selectable output at terminal 46 is inverted

i002: 0

Binary selectable output at terminal 48 is not inverted

(G200)

1

Binary selectable output at terminal 48 is inverted

 

 

i003: 0

Binary selectable output at terminal 50 is not inverted

 

1

Binary selectable output at terminal 50 is inverted

 

i004: 0

Binary selectable output at terminal 52 is not inverted

 

1

Binary selectable output at terminal 52 is inverted

P771

Source for output value at binary output 1

*

Selection of binector to be injected at binary selectable output, terminal 46

 

(G112)

0 = binector B0000

1 = binector B0001

(G200)

etc.

 

 

 

P772

Source for output value at binary output 2

*

Selection of binector to be injected at binary selectable output, terminal 48

 

(G112)

0 = binector B0000

1 = binector B0001

(G200)

etc.

 

 

 

P773

Source for output value at binary output 3

*

Selection of binector to be injected at binary selectable output, terminal 50

 

(G112)

0 = binector B0000

1 = binector B0001

 

 

etc.

 

 

P774

Source for output value at binary output 4

*

Selection of binector to be injected at binary selectable output, terminal 52

 

(G112)

0 = binector B0000

1 = binector B0001

 

 

etc.

 

 

P775

Delay for output value at binary output 1

 

The logic level at the binary selectable output changes only if the internal

(G112)

signal level remains constant for the set delay period (internal signal level

(G200)

changes which do not last as long as this delay period are not switched

 

through to the output)

P776

Delay for output value at binary output 2

 

The logic level at the binary selectable output changes only if the internal

(G112)

signal level remains constant for the set delay period (internal signal level

(G200)

changes which do not last as long as this delay period are not switched

 

through to the output)

 

 

P777

Delay for output value at binary output 3

 

The logic level at the binary selectable output changes only if the internal

(G112)

signal level remains constant for the set delay period (internal signal level

 

changes which do not last as long as this delay period are not switched

 

through to the output)

 

 

P778

Delay for output value at binary output 4

 

The logic level at the binary selectable output changes only if the internal

(G112)

signal level remains constant for the set delay period (internal signal level

 

changes which do not last as long as this delay period are not switched

 

through to the output)

0 to 1

1

All binector numbers 1

All binector numbers 1

All binector numbers 1

All binector numbers 1

0 to 10000 [ms] 1ms

0 to 10000 [ms] 1ms

0 to 10000 [ms] 1ms

0 to 10000 [ms] 1ms

Ind: 4

P052

= 3

FS=0

P051

= 40

Type: O2

Online

Ind: None

P052

= 3

FS=0

P051

= 40

Type: L2

Online

 

 

 

Ind: None

P052

= 3

FS=0

P051

= 40

Type: L2

Online

 

 

 

Ind: None

P052

= 3

FS=0

P051

= 40

Type: L2

Online

 

 

 

Ind: None

P052

= 3

FS=0

P051

= 40

Type: L2

Online

 

 

 

Ind: None

P052

= 3

FS=0

P051

= 40

Type: O2

Online

 

 

 

Ind: None

P052

= 3

FS=0

P051

= 40

Type: O2

Online

 

 

 

Ind: None

P052

= 3

FS=0

P051

= 40

Type: O2

Online

 

 

 

Ind: None

P052

= 3

FS=0

P051

= 40

Type: O2

Online

SIEMENS Energy & Automation

10-77

SIMOREG DC Master Base Drive Panel Operating Instructions

 