PNU

 

Description

Value range

No. indices

See

 

 

 

 

[Unit]

Factory

Change

 

 

 

 

Steps

setting

(Access /

 

 

 

 

 

Type

Status)

 

P453

 

Source for "Enable zero marker counter" command [SW 1.9 and later]

All binector numbers

Ind: 2

P052 = 3

*

 

Selection of binector to control enabling of the zero marker counter

1

FS=1

P051 = 40

 

BDS

 

 

Type: L2

off-line

 

 

0 = binector B0000

 

 

 

 

 

 

 

 

 

 

(G145)

 

1 = binector B0001

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

10.23 Connector selector switches

(see also Section 8, Function Diagram Sheet G124 of Operating Instructions 6RX1700-0AD**)

P455

Source for inputs of connector selector switch 1

[SW 1.9 and later]

*

Selection of connectors for the input signals for connector selector switch 1.

 

(G124)

0

= connector K0000

 

 

1

= connector K0001

 

 

etc.

 

 

 

 

P456

Source for control of connector selector switch 1

[SW 1.9 and later]

*

Selection of binectors to control connector selector switch 1.

 

(G124)

0

= binector B0000

 

 

1

= binector B0001

 

 

etc.

 

 

 

 

P457

Source for inputs of connector selector switch 2

[SW 1.9 and later]

*

Selection of connectors for the input signals for connector selector switch 2.

 

(G124)

0

= connector K0000

 

 

1

= connector K0001

 

 

etc.

 

 

 

 

P458

Source for control of connector selector switch 2

[SW 1.9 and later]

*

Selection of binectors to control connector selector switch 2.

 

(G124)

0

= binector B0000

 

 

1

= binector B0001

 

 

etc.

 

 

 

 

 

All connector numbers

1

All binector numbers 1

All connector numbers

1

All binector numbers 1

Ind: 3

P052

= 3

FS=0

P051

= 40

Type: L2

off-line

 

 

 

Ind: 2

P052

= 3

FS=0

P051

= 40

Type: L2

off-line

 

 

 

Ind: 3

P052

= 3

FS=0

P051

= 40

Type: L2

off-line

 

 

 

Ind: 2

P052

= 3

FS=0

P051

= 40

Type: L2

off-line

 

 

 

10.24 Motorized potentiometer

(see also Section 8, Sheet G126 of Operating Instructions 6RX1700-0AD**)

P460

Control word for motorized potentiometer ramp-function generator

*

0

The motorized potentiometer ramp generator is bypassed in

FDS

 

Automatic mode (same effect as for P462 and P463 = 0.01, i.e.

(G126)

 

the generator output is made to follow the automatic setpoint

 

without delay)

 

 

1Motorized potentiometer ramp generator is active in Manual and Automatic modes

P461

Source for setpoint in Automatic mode

*

Selection of the connector to be applied as the Automatic setpoint to the

FDS

ramp-function generator in the motorized potentiometer

 

(G126)

0 = connector K0000

 

1 = connector K0001

 

etc.

 

 

P462

Ramp-up time for motorized potentiometer

FDS

 

(G126)

 

P463

Ramp-down time for motorized potentiometer

FDS

 

(G126)

 

0 to 1

1

All connector numbers

1

0.01to 300.00

[s]

0.01s

0.01to 300.00

[s]

0.01s

Ind: 4

P052

= 3

FS=1

P051

= 40

Type: O2

Offline

Ind: 4

P052

= 3

FS=0

P051

= 40

Type: L2

Offline

Ind: 4

P052

= 3

FS=10.00

P051

= 40

Type: O2

Online

Ind: 4

P052

= 3

FS=10.00

P051

= 40

Type: O2

Online

SIEMENS Energy & Automation

10-49

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 170
Image 170
Siemens 6RA70 specifications Connector selector switches, Motorized potentiometer, 10-49