PNU

Description

Value range [Unit] Steps

No. indices Factory setting Type

See Change (Access / Status)

P696

Source for selection of "Stop speed controller I component" function

*

Selection of binector to control the "Stop I component" function

BDS

0 = binector B0000

 

(G152)

1 = binector B0001

 

etc.

 

When the binector selected in P696 changes to the log. "1" state, the I

 

component of the speed controller is stopped.

 

 

P697

Source for selection of enabling of dv/dt injection

*

Selection of binector to control enabling of dv/dt injection (state "1" =

BDS

enable)

 

(G153)

0 = binector B0000

 

1 = binector B0001

 

etc.

 

 

P698

Source for selection of enabling command for speed-dependent speed

*controller PI / P function switchover

BDS

Selection of binector to control enabling of the speed-dependent PI / P

(G152)

controller switchover function (see also P222)

0 = binector B0000

 

 

1 = binector B0001

 

etc.

All binector numbers

Ind: 2

P052

= 3

1

FS=0

P051

= 40

 

Type: L2

Offline

All binector numbers

Ind: 2

P052

= 3

1

FS=1

P051

= 40

 

Type: L2

Offline

All binector numbers

Ind: 2

P052

= 3

1

FS=1

P051

= 40

 

Type: L2

Offline

10.37 Analog inputs (main actual value, main setpoint, selectable inputs)

(see also Section 8, Sheets G113 and G114 of Operating Instructions 6RX1700-0AD**)

Analog input terminals 4 / 5 (main setpoint)

P700

Signal type of "Main setpoint" analog input

*

0 =

Voltage input 0 to ±10 V

 

(G113)

1 =

Current input 0 to ±20 mA

 

2 =

Current input 4 to 20 mA

P701

Normalization of "Main setpoint" analog input

FDS

This parameter specifies the percentage value which is generated for an

input voltage of 10V (or an input current of 20mA) at the analog input.

 

(G113)

The following generally applies:

 

For voltage input:

 

 

P701 [%] =10 V Y

X .. Input voltage in volts

 

 

X

Y .. % value which is generated for input

 

 

 

 

With current input:

voltage X

 

 

 

P701 [%] = 20 mA Y

X .. Input current in mA

 

 

X

Y .. % value which is generated for input

 

 

 

 

 

 

current X

 

 

P702

Offset for "Main setpoint" analog input

(G113)

 

 

 

P703

Mode of signal injection at "Main setpoint" analog input

*

0 =

Injection of signal with sign

 

(G113)

1 =

Injection of absolute value of signal

2 =

Injection of signal with sign, inverted

 

 

3 =

Injection of absolute value of signal, inverted

 

 

P704

Source for selection of sign reversal at "Main setpoint" analog input

*

Selection of binector to control sign reversal at the analog input ("1" state

 

(G113)

= reverse sign)

 

 

 

 

 

0 = binector B0000

 

 

1 = binector B0001

 

 

etc.

 

 

 

 

P705

Filtering time for "Main setpoint" analog input

(G113)

Note: Hardware filtering of approximately 1 ms is applied as standard.

 

 

 

0 to 2

1

-1000.0 to 1000.0 [%] 0.1%

-200.00 to 199.99 [%] 0.01%

0 to 3

1

All binector numbers 1

0 to 10000 [ms] 1ms

Ind: None

P052

= 3

FS=0

P051

= 40

Type: O2

Offline

 

 

 

Ind: 4

P052

= 3

FS=100.0

P051

= 40

Type: I2

Online

Ind: None

P052

= 3

FS=0.00

P051

= 40

Type: I2

Online

Ind: None

P052

= 3

FS=0

P051

= 40

Type: O2

Offline

 

 

 

Ind: None

P052

= 3

FS=0

P051

= 40

Type: L2

Offline

Ind: None

P052

= 3

FS=0

P051

= 40

Type: O2

Online

SIEMENS Energy & Automation

10-71

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 192