5.2 140ADC to 850ADC Base Drive Panels, 3AC 460V, 1 & 4Q

 

Rated supply voltage

 

 

V

 

 

 

 

 

3 Phase

 

 

 

 

 

armature 1)

 

 

 

 

 

 

 

460 (+10% / – 5%)

 

 

 

 

 

Rated input current

 

 

A

129.8

 

187.2

 

 

234.1

 

377.6

 

 

448.2

 

727

 

 

armature + field 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan type

 

 

V

Internal 24VDC

 

 

 

 

1 Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air flow rate

ft3/min

 

100

 

 

 

 

570

 

 

 

 

1300

 

 

Fan noise level

 

dBA

 

40

 

 

 

 

76

 

 

 

 

85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated supply voltage field

 

V

 

 

 

1 Phase 460 (+10%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated frequency

 

 

Hz

45 to 65 Hz self adapting (armature and field are

 

 

 

 

 

independent)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated DC voltage 3)

 

 

V

 

 

 

500

 

 

 

 

 

 

 

 

Rated DC armature current

 

A

140

 

210

 

255

 

430

 

 

510

 

850

 

 

Overload capability 60s

7)

 

 

 

 

150% of rated DC current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated output @ 500 VDC

 

Hp

75

 

125

 

150

 

250

 

 

300

 

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated output @ 240 VDC

 

Hp

40

 

60

 

75

 

125

 

 

150

 

250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power loss at rated DC current

 

W

740

 

1000

 

1300

 

1915

 

 

2180

 

3850

 

 

(approximately)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated DC voltage field

 

 

V

 

 

 

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated DC field current

 

 

A

 

15

 

 

25

 

 

 

 

30

 

 

Operational ambient

 

 

°C

 

 

 

 

 

0 to 45 at Irated

 

 

 

 

 

temperature

 

 

 

 

 

 

 

 

fan-cooled 4)

 

 

 

 

 

Storage and transport

 

 

°C

 

 

 

 

 

– 25 to +70

 

 

 

 

 

temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation altitude above sea

 

 

 

 

1000 m at rated DC current 5)

 

 

 

 

level

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control stability

 

 

 

n = 0.006% of the rated motor speed, valid for pulse

 

 

 

 

 

encoder operation and digital setpoint

 

 

 

 

 

 

 

 

 

n = 0.1% of the rated motor speed, valid for analog

 

 

 

 

 

tachometer or analog setpoint 6)

 

 

 

 

 

Degree of protection

 

 

 

 

 

 

Open Chassis (IP00)

 

 

 

 

 

 

 

 

 

 

 

Dimensions

 

 

 

Refer to dimension drawings in Section 6

 

Weights (approx.)

 

 

Lbs.

90

 

 

 

160

 

 

210

 

 

 

 

 

 

95

 

145

 

 

 

 

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5-2

Siemens Energy & Automation

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 27
Image 27
Siemens 6RA70 specifications 140ADC to 850ADC Base Drive Panels, 3AC 460V, 1 & 4Q, 140 210 255 430 510 850