Siemens 6RA70 specifications 10-14, R065 Software identifiers, P067 Load class

Models: 6RA70

1 232
Download 232 pages 59.99 Kb
Page 135
Image 135

 

PNU

 

Description

 

 

Value range

No. indices

See

 

 

 

 

 

 

 

[Unit]

Factory

Change

 

 

 

 

 

 

 

Steps

setting

(Access /

 

 

 

 

 

 

 

 

Type

Status)

 

r064

 

Board compatibility

 

 

Ind: 5

P052 = 3

 

(G101)

 

Compatibility identifier of boards in locations 1 to 3 of electronics box.

 

Type: O2

 

 

 

 

 

 

 

 

The compatibility identifier is bit-coded. To ensure the compatibility of a

 

 

 

 

 

 

 

 

 

 

 

 

board, it must have a "1" setting at the same bit location of the parameter

 

 

 

 

 

 

value as the CUD (in location 1 / index i001).

 

 

 

 

 

 

Indices:

 

 

 

 

 

 

 

 

i001:

Compatibility identifier of board in location 1

 

 

 

 

 

 

i002:

Compatibility identifier of board in slot D

 

 

 

 

 

 

i003:

Compatibility identifier of board in slot E

 

 

 

 

 

 

i004:

Compatibility identifier of board in slot F

 

 

 

 

 

 

i005:

Compatibility identifier of board in slot G

 

 

 

 

 

 

Example:

 

 

 

 

 

 

 

 

Index

Value

Bit representation

Compatible with CUD

 

 

 

 

 

 

i001

253

0000 0000 1111 1101

 

 

 

 

 

 

 

i002

002

0000 0000 0000 0010

no

 

 

 

 

 

 

i003

001

0000 0000 0000 0001

yes

 

 

 

 

 

 

 

 

 

 

 

 

r065

 

Software identifiers

 

 

Ind: 5

P052 = 3

 

(G101)

 

Extended software version identifiers in locations 1, 2, and 3 of the

 

Type: O2

 

 

 

 

 

 

 

 

electronics box

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indices:

 

 

 

 

 

 

 

 

i001:

Software identifier of the board in location 1

 

 

 

 

 

 

i002:

Software identifier of the board in slot D

 

 

 

 

 

 

i003:

Software identifier of the board in slot E

 

 

 

 

 

 

i004:

Software identifier of the board in slot F

 

 

 

 

 

 

i005:

Software identifier of the board in slot G

 

 

 

 

 

 

 

 

 

 

 

 

 

P067

 

Load class

 

[SW1.8 and later]

1 to 5

Ind: None

P052 = 3

*

 

1 Load class DC I

 

1

FS=1

P051 = 40

 

 

 

 

 

Type: O2

off-line

 

(G101)

 

2 Load class DC II

 

 

 

 

 

 

 

 

 

 

3 Load class DC III

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 Load class DC IV

 

 

 

 

 

 

5

US rating

 

 

 

 

 

 

 

 

The load classes are described in Chapter 3.4.1.

 

 

 

 

 

 

Depending on the load class selected, the device rated DC of the

 

 

 

 

 

 

SIMOREG DC Master is reduced to a value of different magnitude to suit

 

 

 

 

 

 

the power section and load class.

 

 

 

 

 

 

 

The current value of the device rated DC is indicated in parameter r072.002.

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

 

If the device rated DC is reduced via parameter P076.001, the lesser of the

 

 

 

 

 

 

two values is active.

 

 

 

 

 

 

 

If you set a value of > 1 in P067, you must ensure that the "Dynamic

 

 

 

 

 

 

overload capability of power module“ is enabled, i.e. a value of > 0 must be

 

 

 

 

 

 

set in parameter P075.

 

 

 

 

 

 

 

The SIMOREG DC Master does not monitor for compliance with the criteria

 

 

 

 

 

 

of the load class set in parameter P067. If permitted by the power module,

 

 

 

 

 

 

the unit can operate for overload periods in excess of those defined by the

 

 

 

 

 

 

load class. The permissible overload period for the installed power module

 

 

 

 

 

 

is always longer than the period defined for the load class. The SIMOREG

 

 

 

 

 

 

DC Master does monitor the actual permissible overload period for the

 

 

 

 

 

 

power module. See Section 9.15.

 

 

 

 

 

 

 

 

 

 

 

 

 

r068

 

Options according to rating plate

 

 

Ind: None

P052 = 3

 

(G101)

0

No option

 

 

 

Type: 02

 

 

 

 

 

 

 

 

 

1 Option L04 (low voltage, 85V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 Option K00 (terminal expansion)

 

 

 

 

 

 

3

L04 and K00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10-14

SIEMENS Energy & Automation

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 135
Image 135
Siemens 6RA70 specifications 10-14, R065 Software identifiers, P067 Load class, R068 Options according to rating plate