PNU

Description

Value range [Unit] Steps

No. indices Factory setting Type

See Change (Access / Status)

P083

Selection of actual speed value

*

0

Actual speed value is not yet selected (fixed value 0%)

FDS

1

Actual speed value supplied by "Main actual value” channel

 

(G151)

 

(K0013) (terminals XT.103, XT.104)

 

 

2Actual speed value supplied by "Actual speed from pulse encoder” channel (K0040)

3Actual speed value supplied by "Actual EMF" channel (K0287), but weighted with P115 (operation without tacho)

Note:

The effectiveness of the overspeed monitoring function (see Section 8, function diagram G188) is restricted, since very high motor speeds can be reached if the EMF is utilized as the actual speed value when the actual field current value is too low.

4Actual speed value is wired up freely (selected in P609)

P084

Selection of closed-loop speed / current or torque control

*

1

Operation under closed-loop speed control

 

(G160)

2

Operation under closed-loop current / torque control

 

 

The setpoint supplied by the ramp-function generator output is

 

 

input as a current or torque setpoint (speed controller is

 

 

bypassed)

P085

Wait period after cancellation of inching command

 

After an inching command has been cancelled, the drive dwells in operating

 

state o1.3 for the time period set in this parameter with the controllers

 

disabled, but the line contactor closed. This wait period does not commence

 

until n<nmin (P370, P371) is reached. If a new inching command is input

 

within this period, then the drive switches to the next operating state (o1.2 or

 

lower). However, if the time runs out without a new inching command being

 

entered, then the line contactor drops out and the drive switches to

 

operating state o7 (see also Section 9).

 

 

P086

Voltage failure period for automatic restart

 

If the voltage fails (F001, F004) at one of the terminals 1U1, 1V1, 1W1, 3U1,

 

3W1, 5U1 or 5W1, or if it drops below a certain threshold (F006

 

undervoltage) or exceeds a certain threshold (F007 overvoltage), or its

 

frequency is too low (F008 frequency < P363) or too high (F009 frequency >

 

P364), or if the actual field current drops to below 50% of the field current

 

setpoint for more than 0.5s (F005), then the corresponding fault message is

 

activated only if the fault condition has not been eliminated within the

 

"Automatic restart" period set in this parameter.

 

The gating pulses and controllers are disabled while the fault conditions are

 

present. The converter dwells in operating state o4 (in the case of armature

 

line voltage fault) or o5 (in the case of field line voltage or field current fault)

 

or in o13.

 

 

Setting this parameter to 0.00s deactivates the "Automatic restart" function.

 

NOTE:

 

 

Setting values higher than 2.00s are effective only in relation to the voltages

 

at terminals 1U1, 1V1, 1W1, 3U1 and 3W1.

 

A "restart time" of 2.00 s is operative in this case for the voltage at terminals

 

5U1 and 5W1 (electronics power supply).

 

 

P087

Brake release time

(G140)

-10.00 to -0.01 s

The "Release brake" command is delayed in relation to enabling of the

 

 

gating pulses for thyristors and controllers (i.e. operating state I, II or --) by

 

the delay time set in this parameter. During this period, the motor rotates

 

against the closed brake. This setting is useful, for example, for vertical

 

loads.

 

 

0.00 to +10.00 s

 

When a "Switch-on" or "Inching" or "Crawling" command is input with

 

"Operating enable", the drive dwells in operating state o1.0 for the delay

 

period set in this parameter; the internal controller enabling signal, and thus

 

enabling of the thyristor gating pulses, do not take effect until the delay

 

period has elapsed so as to give the holding brake time to open.

0 to 4

1

1 to 2

1

0.0to 60.0

[s]

0.1s

0.00to 10.00

[s]

0.01s

-10.00 to 10.00 [s]

0.01s

Ind: 4

P052

= 3

FS=0

P051

= 40

Type: O2

Offline

Ind: None

P052

= 3

FS=1

P051

= 40

Type: O2

Offline

 

 

 

Ind: None

P052

= 3

FS=10.0

P051

= 40

Type: O2

Online

Ind: None

P052

= 3

FS=0.40

P051

= 40

Type: O2

Online

Ind: None

P052

= 3

FS=0.00

P051

= 40

Type: I2

Online