Siemens 6RA70 specifications 10-35

Models: 6RA70

1 232
Download 232 pages 59.99 Kb
Page 156
Image 156

PNU

Description

Value range [Unit] Steps

No. indices Factory setting Type

See Change (Access / Status)

r218

Indication of the active integration time of the speed controller

(G151)

[SW 1.7 and later]

(G152)

 

r219

Display of effective P gain of speed controller

(G151)

 

(G152)

 

0.010 to 10.000 [s]

0.001s

0.01to 200.00

Ind: None

P052 = 3

Type: O2

 

 

 

Ind: None

P052 = 3

Type: O2

 

 

 

P221

Speed controller: Hysteresis for speed-dependent PI/P controller

FDS

switchover

[SW 1.9 and later]

See P222 for further details.

(G152)

 

 

P222

Speed controller: Speed-dependent switchover threshold for PI / P

FDS

controller

 

0.00 Automatic switchover from PI to P controller deactivated.

 

(G152)

> 0.00 Depending on the actual speed (K0166), the PI controller

 

 

switches over to a P controller if the speed drops below the

 

 

threshold set in parameter P222. The integrator is not switched

 

 

in again (with value of 0) until the actual speed is > P222 +

 

 

P221.

 

 

This function allows the drive to be stopped without overshoot

 

 

using a zero setpoint with the controllers enabled.

 

 

This function is active only if the binector selected in P698 is in

 

 

the log. "1" state.

 

 

 

0.00to 100.00

[%]

0.01% of maximum speed

0.00to 10.00

[%]

0.01% of maximum speed

Ind: 4

P052

= 3

FS=2.00

P051

= 40

Type: O2

Online

 

 

 

Ind: 4

P052

= 3

FS=0.00

P051

= 40

Type: O2

Online

 

 

 

Setting values for speed controller

P223

Control word for speed controller precontrol

*

0

Speed controller precontrol disabled

FDS

1

Speed controller precontrol acts as torque setpoint (is added to

(G152)

 

n controller output)

 

 

P224

Control word for speed controller I component

*

0

Set controller I component to 0 (i.e. to achieve a pure P

FDS

 

controller)

(G152)

 

1

Controller I component is active

 

 

The I component is stopped when a torque or current limit is

 

 

reached

2Controller I component is active

The I component is stopped when a torque limit is reached

3Controller I component is active

The I component is stopped only when ±199.99% is reached

P225

Speed controller P gain

FDS

See also setting values for "Speed controller adaptation" function (P550 to

P559).

 

(G151)

This parameter is set automatically during the speed controller optimization

run (P051=26).

 

 

 

P226

Speed controller reset time

FDS

This parameter is set automatically during the speed controller optimization

(G151)

run (P051=26).

 

0 to 1

1

0 to 3

1

0.10to 200.00

0.010 to 10.000 [s]

0.001s

Ind: 4

P052

= 3

FS=0

P051

= 40

Type: O2

Offline

 

 

 

Ind: 4

P052

= 3

FS=1

P051

= 40

Type: O2

Offline

Ind: 4

P052

= 3

FS=3.00

P051

= 40

Type: O2

Online

 

 

 

Ind: 4

P052

= 3

FS=0,650

P051

= 40

Type: O2

Online

Speed controller droop

Function: A parameterizable feedback loop can be connected in parallel to the I and P components of the speed controller (acts on summation point of setpoint and actual value).

P227

Speed controller droop

0.0 to 10.0

Ind: 4

P052

= 3

 

A 10% speed droop setting causes a 10% deviation in the speed from the

[%]

FS=0.0

P051

= 40

FDS

0.1%

Type: O2

Online

setpoint at a 100% controller output (100% torque or armature current

 

 

 

 

 

(G151)

setpoint) ("softening" of closed-loop control).

 

 

 

 

See also P562, P563, P630 and P684

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P228

Filter time for speed setpoint

0 to 10000

Ind: 4

P052

= 3

 

Filtering of setpoint by means of a PT1 element.

[ms]

FS=0

P051

= 40

FDS

1ms

Type: O2

Online

This parameter is automatically set to the same value as the speed

 

 

 

 

 

(G152)

controller reset time during the speed controller optimization run (P051=26).

 

 

 

 

It may be useful to parameterize lower values when the ramp-function

 

 

 

 

 

 

 

 

 

 

generator is in use.

 

 

 

 

 

 

 

 

 

 

SIEMENS Energy & Automation

10-35

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 156
Image 156
Siemens 6RA70 specifications 10-35