Limitation at ramp-function generator output (setpoint limiting)

The effective limitations are:

 

 

 

 

Upper limit:

Minimum value of P300 and the four connectors selected with P632

 

 

 

 

Lower limit:

Maximum value of P301 and the four connectors selected with P633

 

 

 

 

Note:

The limiting values for both the positive and negative setpoint limits can have a positive or negative sign. The negative

 

 

setpoint limit, for example, can therefore be parameterized to a positive value and the positive setpoint limit to a negative

 

 

value.

-200.00 to 199.99

 

 

 

P300

Positive limitation at ramp-function generator output

Ind: 4

P052

= 3

FDS

 

 

[%]

FS=100.00

P051

= 40

(G137)

 

 

0.01%

Type: I2

Online

P301

Negative limitation at ramp-function generator output

-200.00 to 199.99

Ind: 4

P052

= 3

FDS

 

 

[%]

FS=-100.00

P051

= 40

(G137)

 

 

0.01%

Type: I2

Online

P302

Select ramp-function generator / ramp-up integrator mode

0 to 3

Ind: 4

P052

= 3

*

0

Normal ramp-function generator operation:

1

FS=0

P051

= 40

FDS

 

Type: O2

Offline

 

Ramp-function generator setting 1 (P303 to P306) is applied.

 

 

 

 

 

 

(G136)

 

When a binary selectable input parameterized as "Ramp-

 

 

 

 

 

function generator setting 2" (P307 to P310)” (selected in P637)

 

 

 

 

 

 

or ”Ramp-function generator setting 3" (P311 to P314)”

 

 

 

 

 

 

(selected in P638), generator setting 2 or 3 is applied as

 

 

 

 

 

 

appropriate.

 

 

 

 

 

1

Ramp-up integrator operation:

 

 

 

 

 

 

When the setpoint is reached for the first time, ramp-function

 

 

 

 

 

 

generator setting 1 is switched over to a ramp-up/down

 

 

 

 

 

 

times = 0

 

 

 

 

 

2

Ramp-up integrator operation:

 

 

 

 

 

 

When the setpoint is reached for the first time, ramp-function

 

 

 

 

 

 

generator setting 1 is switched over to generator setting 2 (P307

 

 

 

 

 

 

to P310)

 

 

 

 

 

3

Ramp-up integrator operation:

 

 

 

 

 

 

When the setpoint is reached for the first time, ramp-function

 

 

 

 

 

 

generator setting 1 is switched over to generator setting 3 (P311

 

 

 

 

 

 

to P314)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ramp-function generator parameter set 1 (see also parameter P330)

 

 

 

 

 

 

0.00 to 650.00

 

 

 

P303

Ramp-up time 1

Ind: 4

P052

= 3

FDS

 

 

[s]

FS=10.00

P051

= 40

(G136)

 

 

0.01s

Type: O2

Online

P304

Ramp-down time 1

0.00 to 650.00

Ind: 4

P052

= 3

FDS

 

 

[s]

FS=10.00

P051

= 40

(G136)

 

 

0.01s

Type: O2

Online

P305

Lower transition rounding 1

0.00 to 100.00

Ind: 4

P052

= 3

FDS

 

 

[s]

FS=0.00

P051

= 40

(G136)

 

 

0.01s

Type: O2

Online

P306

Upper transition rounding 1

0.00 to 100.00

Ind: 4

P052

= 3

FDS

 

 

[s]

FS=0.00

P051

= 40

(G136)

 

 

0.01s

Type: O2

Online

 

 

 

 

 

Ramp-function generator parameter set 2 (see also parameter P330)

 

 

 

 

Ramp-function generator parameter set 2 is selected via the binector parameterized in P637.

 

 

 

P307

Ramp-up time 2

0.00 to 650.00

Ind: 4

P052

= 3

FDS

 

 

[s]

FS=10.00

P051

= 40

(G136)

 

 

0.01s

Type: O2

Online

P308

Ramp-down time 2

0.00 to 650.00

Ind: 4

P052

= 3

FDS

 

 

[s]

FS=10.00

P051

= 40

(G136)

 

 

0.01s

Type: O2

Online

P309

Lower transition rounding 2

0.00 to 100.00

Ind: 4

P052

= 3

FDS

 

 

[s]

FS=0.00

P051

= 40

(G136)

 

 

0.01s

Type: O2

Online

P310

Upper transition rounding 2

0.00 to 100.00

Ind: 4

P052

= 3

FDS

 

 

[s]

FS=0.00

P051

= 40

(G136)

 

 

0.01s

Type: O2

Online

Ramp-function generator parameter set 3 (see also parameter P330)

Ramp-function generator parameter set 3 is selected via the binector parameterized in P638.

P311

Ramp-up time 3

0.00 to 650.00

FDS

 

[s]

(G136)

 

0.01s

Ind: 4

FS=10.00

Type: O2

P052 = 3

P051 = 40 Online