PNU

 

Description

 

Value range

No. indices

See

 

 

 

 

 

[Unit]

Factory

Change

 

 

 

 

 

Steps

setting

(Access /

 

 

 

 

 

 

Type

Status)

 

P706

 

Source for enabling of "Main setpoint" analog input

 

All binector numbers

Ind: None

P052 = 3

*

 

Selection of binector to control enabling of the analog input ("1" state =

1

FS=1

P051 = 40

 

 

 

 

 

Type: L2

Offline

 

(G113)

 

enabled)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 = binector B0000

 

 

 

 

 

 

 

1 = binector B0001

 

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

P707

 

Resolution of "Main setpoint" analog input

 

11 to 14

Ind: None

P052 = 3

*

 

The voltage applied to the analog input is converted to a digital value (A/D

 

[Bit]

FS=12

P051 = 40

 

 

 

 

1 bit

Type: O2

Offline

 

(G113)

 

conversion) for further processing. The method used calculates an average

 

 

 

 

 

 

 

 

 

value of the input voltage over a specific measuring time.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The A/D conversion process produces a scale for the voltage range of 0 to ±

 

 

 

 

 

 

 

10V, the number of steps (divisions) along this scale can be set in P707 (i.e.

 

 

 

 

 

 

 

the smallest possible differentiable change in the input voltage

 

 

 

 

 

 

 

(quantization) can be set in this parameter). The number of scale steps or

 

 

 

 

 

 

 

intervals is referred to as "Resolution".

 

 

 

 

The resolution is normally specified in bits:

±11 bits means 2 * 2048 scale divisions

±12 bits means 2 * 4096 scale divisions

±13 bits means 2 * 8192 scale divisions

±14 bits means 2 * 16384 scale divisions

The following applies:

The higher the resolution, the longer the averaging time and thus also the delay period between the application of an analog step change and the earliest possible moment of availability of the digital value for further processing.

For this reason, it is important to find a compromise between the resolution and delay period.

Param.

Resolution

Quantization

Delay period

value

better than

 

 

11

± 11 bits

4.4 mV

0.53 ms

12

± 12 bits

2.2 mV

0.95 ms

13

± 13 bits

1.1 mV

1.81 ms

14

± 14 bits

0.56 mV

3.51 ms

If the analog input is operating as a current input (0 to 20 mA or 4 to 20 mA), the above applies analogously.

Analog input terminals 6 / 7 (analog selectable input 1)

P710

Signal type of "Analog selectable input 1"

0 to 2

Ind: None

P052

= 3

*

0 =

Voltage input 0 to ±10 V

1

FS=0

P051

= 40

 

 

Type: O2

Offline

(G113)

1 =

Current input 0 to ±20 mA

 

 

 

 

 

2 =

Current input 4 to 20 mA

 

 

 

 

P711

Normalization of "Analog selectable input 1"

-1000.0 to 1000.0

Ind: 4

P052

= 3

 

This parameter specifies the percentage value which is generated for an

[%]

FS=100.0

P051

= 40

FDS

0.1%

Type: I2

Online

input voltage of 10V (or an input current of 20mA) at the analog input.

 

 

 

 

 

 

 

 

 

(G113)

The following generally applies:

 

 

 

 

 

For voltage input:

 

 

 

 

 

 

P711

[%] =10 V Y

X .. Input voltage in volts

 

 

 

 

 

 

X

Y .. % value which is generated for input

 

 

 

 

 

 

 

 

 

 

 

 

With current input:

voltage X

 

 

 

 

 

 

 

 

 

 

 

P711 [%] = 20 mA Y

X .. Input current in mA

 

 

 

 

 

 

X

Y .. % value which is generated for input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

current X

 

 

 

 

 

 

 

 

 

 

P712

Offset for "Analog selectable input 1"

-200.00 to 199.99

Ind: None

P052

= 3

 

 

 

 

[%]

FS=0.00

P051

= 40

(G113)

 

 

 

0.01%

Type: I2

Online

P713

Mode of signal injection at "Analog selectable input 1"

0 to 3

Ind: None

P052

= 3

*

0 =

Injection of signal with sign

1

FS=0

P051

= 40

 

 

Type: O2

Offline

(G113)

1 =

Injection of absolute value of signal

 

 

 

 

 

2 =

Injection of signal with sign, inverted

 

 

 

 

 

 

 

 

 

 

3 =

Injection of absolute value of signal, inverted

 

 

 

 

 

 

 

 

 

 

 

10-72

 

 

 

SIEMENS Energy & Automation

 

 

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 193
Image 193
Siemens 6RA70 10-72, P707 Resolution of Main setpoint analog input, P711 Normalization of Analog selectable input