Fault

 

Description

 

 

No.

 

Cause as a function of fault value

 

 

 

Further information (r047.002 to r047.016)

 

 

 

(r047.001, r949.001 or r949.009 with acknowledged error)

 

 

 

 

 

 

 

 

 

 

 

 

 

31Thyristor unable to block (X11 or X21)

32Thyristor unable to block (X12 or X22)

33Thyristor unable to block (X13 or X23)

34Thyristor unable to block (X14 or X24)

35Thyristor unable to block (X15 or X25)

36Thyristor unable to block (X16 or X26)

9.1.2.12Internal faults

F062 Fault in parameter memory (active in all operating states)

Software monitoring of correct functioning of the EEPROM module (non-volatile memory) on the A7009 board.

The EEPROM values contains all data which must be protected in the case of a power failure (i.e. parameter values and process data which must remain stored during power failures).

The following are monitored:

Connection between the A7001 electronics board and the EEPROM on the A7009 backplane wiring assembly

Whether the parameter values stored on the EEPROM are within the permissible value range

Whether data are being correctly stored on the EEPROM. For this purpose, values are read and checked for correctness after they are transferred to the module

Whether the checksum of the non-volatile process data in the EEPROM is correct

Possible causes for all fault types:

Excessive EMC-related interference is present (e.g. due to unprotected contactors, unscreened cables, loose shield connections)

Fault value:

r047 Index 002 to 016:

1Connection to EEPROM is faulty Possible fault causes

A7001 electronics board is defective

A7009 backplane wiring assembly is defective

Plug-in connection X109 is defective

2

Parameter value is outside permissible value range

i002

Number of faulty parameter

 

Possible fault causes

i003

Index of faulty parameter

 

“Restore to default value” has never been executed

i004

Faulty parameter value

 

with this software (e.g. after software replacement)

 

 

A7009 backplane wiring assembly is defective

 

Possible remedy:

 

 

 

Acknowledge fault, execute “Restore to default value”

 

 

 

and start up the drive again

 

 

3

Parameter value cannot be stored on EEPROM

i002

Address of fault memory location

 

Possible fault causes

i003

Faulty value in EEPROM

 

A7001 electronics board is defective

i004

Correct parameter value

 

A7009 backplane wiring assembly is defective

 

 

 

Plug-in connection X109 is defective

 

 