PNU

 

Description

Value range

No. indices

See

 

 

 

 

[Unit]

Factory

Change

 

 

 

 

Steps

setting

(Access /

 

 

 

 

 

Type

Status)

 

P119

 

Rated speed

0.0 to 199.9

Ind: 4

P052 = 3

 

 

 

Speed at which an actual EMF value as set in parameter P118 is reached at

[%]

FS=100.0

P051 = 40

 

FDS

 

0.1%

Type: O2

Offline

 

 

full field (according to parameter P102).

 

 

 

 

 

 

This parameter is set automatically during the optimization run for field

 

 

 

 

(G165)

 

weakening (P051=27) and specifies in this case the field-weakening

 

 

 

 

 

activation limit speed.

 

 

 

 

 

 

 

 

 

 

 

 

Note:

 

 

 

 

 

 

As regards the closed-loop field-weakening control, only the ratio between

 

 

 

 

 

 

P118 and P119 is relevant. When the setting in P100, P101 or P110 is

 

 

 

 

 

 

changed subsequently, the field-weakening optimization run need not be

 

 

 

 

 

 

repeated. However, P119 then no longer defines the field-weakening

 

 

 

 

 

 

activation limit speed.

 

 

 

 

 

 

When the setting in parameter P102 is changed subsequently, the field-

 

 

 

 

 

 

weakening optimization run must be repeated, the same applies if the

 

 

 

 

 

 

maximum speed setting is subsequently re-adjusted.

 

 

 

 

 

 

 

 

 

 

Magnetization characteristic (field characteristic)

Parameters P120 to P139 determine the curve shape of the magnetization characteristic (field characteristic) in normalized representation (see example field characteristic below for further details).

Note:

When the setting in parameter P102 is changed subsequently, the field-weakening optimization run must be repeated, because this alters the degree of saturation and thus the shape of the magnetization characteristic. (When parameter P100, P101 or P110, or the maximum speed adjustment, is subsequently altered, the settings in P120 to P139 remain the same, but the values in P118 and/or P119 are changed).

r120

Field current for 0% motor flux (field characteristic, point no. 0)

0.0

 

Ind: 4

P052

= 3

FDS

 

[% of P102]

 

Type: O2

 

 

(G165)

 

0.1% of P102

 

 

 

 

(G166)

 

 

 

 

 

 

P121

Field current for 5% motor flux (field characteristic, point no. 1)

0.0 to 100.0

 

Ind: 4

P052

= 3

FDS

 

[%]

 

FS=3.7

P051

= 40

(G165)

 

0.1% of P102

 

Type: O2

Offline

(G166)

 

 

 

 

 

 

P122

Field current for 10% motor flux (field characteristic, point no. 2)

0.0 to 100.0

 

Ind: 4

P052

= 3

FDS

 

[% of P102]

 

FS=7.3

P051

= 40

(G165)

 

0.1% of P102

 

Type: O2

Offline

(G166)

 

 

 

 

 

 

P123

Field current for 15% motor flux (field characteristic, point no. 3)

0.0 to 100.0

 

Ind: 4

P052

= 3

FDS

 

[% of P102]

 

FS=11.0

P051

= 40

(G165)

 

0.1% of P102

 

Type: O2

Offline

(G166)

 

 

 

 

 

 

P124

Field current for 20% motor flux (field characteristic, point no. 4)

0.0 to 100.0

 

Ind: 4

P052

= 3

FDS

 

[% of P102]

 

FS=14.7

P051

= 40

(G165)

 

0.1% of P102

 

Type: O2

Offline

(G166)

 

 

 

 

 

 

P125

Field current for 25% motor flux (field characteristic, point no. 5)

0.0 to 100.0

 

Ind: 4

P052

= 3

FDS

 

[% of P102]

 

FS=18.4

P051

= 40

(G165)

 

0.1% of P102

 

Type: O2

Offline

(G166)

 

 

 

 

 

 

P126

Field current for 30% motor flux (field characteristic, point no. 6)

0.0 to 100.0

 

Ind: 4

P052

= 3

FDS

 

[% of P102]

 

FS=22.0

P051

= 40

(G165)

 

0.1% of P102

 

Type: O2

Offline

(G166)

 

 

 

 

 

 

P127

Field current for 35% motor flux (field characteristic, point no. 7)

0.0 to 100.0

 

Ind: 4

P052

= 3

FDS

 

[% of P102]

 

FS=25.7

P051

= 40

(G165)

 

0.1% of P102

 

Type: O2

Offline

(G166)

 

 

 

 

 

 

P128

Field current for 40% motor flux (field characteristic, point no. 8)

0.0 to 100.0

 

Ind: 4

P052

= 3

FDS

 

[% of P102]

 

FS=29.4

P051

= 40

(G165)

 

0.1% of P102

 

Type: O2

Offline

(G166)

 

 

 

 

 

 

P129

Field current for 45% motor flux (field characteristic, point no. 9)

0.0 to 100.0

 

Ind: 4

P052

= 3

FDS

 

[% of P102]

 

FS=33.1

P051

= 40

(G165)

 

0.1% of P102

 

Type: O2

Offline

(G166)

 

 

 

 

 

 

P130

Field current for 50% motor flux (field characteristic, point no. 10)

0.0 to 100.0

 

Ind: 4

P052

= 3

FDS

 

[% of P102]

 

FS=36.8

P051

= 40

(G165)

 

0.1% of P102

 

Type: O2

Offline

(G166)

 

 

 

 

 

 

10-24

 

 

SIEMENS Energy & Automation

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 145
Image 145