P143

 

Setting the maximum speed for pulse encoder operation

1.0 to 6500.0

Ind: 4

P052

= 3

 

FDS

 

The speed set in this parameter corresponds to an actual speed (K0040) of

[rev/min]

FS=500.0

P051

= 40

 

(G145)

 

0.1rev/min

Type: O4

Online

 

100%.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control parameters for speed sensing with pulse encoder P144 to P147:

P144 and P147 determine the basic setting for actual speed sensing by means of pulse encoder (single or multiple evaluation of pulse encoder signals and nominal measuring time) and thus also define the lowest possible measurable speed (minimum speed).

P145 and P146 can be used in special cases to extend the measurable speed range down to even lower speeds, on the basis of the minimum speed defined by the settings in P144 and P147.

P144

Multiple evaluation of encoder signals

*

0

1x evaluation of pulse encoder signals

FDS

1

2x evaluation of pulse encoder signals (for encoder types 1, 1a, 2)

(G145)

2

4x evaluation of pulse encoder signals (for encoder types 1, 1a)

Note:

 

 

 

 

In contrast to the 1x evaluation method, 2x or 4x evaluation reduces the

 

minimum measurable speed by a factor of 2 or 4 respectively, but may

 

produce an "unsteady" actual speed value on encoders with unequal

 

pulse/pause ratio or without an exact 90° displacement between encoder

 

signals.

 

 

 

P145

Automatic measuring range switchover for measurement of low

*speeds - switchover of multiple evaluation

FDS

0

Automatic switchover of multiple evaluation of pulse encoder

(G145)

 

signals OFF (i.e. P144 is always active)

1

Automatic switchover of multiple evaluation of pulse encoder

 

 

 

signals ON (i.e. when P144 = 0, 2x evaluation is selected for low

 

 

speeds and 4x evaluation for very low speeds. When P144 = 1,

 

 

4x evaluation is selected for low speeds)

 

 

As opposed to P145 = 0, this setting reduces the minimum

 

 

measurable speed by up to a factor of 4.

 

Caution:

 

 

Switching over the multiple evaluation method for encoder pulses also

 

affects the position sensing function in the measuring channel. For this

 

reason, this setting may not be used in conjunction with positioning

 

operations. Connectors K0042 to K0044 are inoperative when P145 = 1.

 

 

P146

Automatic measuring range switchover for measurement of low

*speeds - switchover of measuring time

FDS

0

Automatic switchover of measuring time OFF

(G145)

 

(i.e. P147 is always active)

1

Automatic switchover of measuring time ON

 

 

 

This setting extends the measuring time for low speeds (based

 

 

on the measuring time set in P147, i.e. when P147 = 0, the

 

 

nominal measuring time is switched over to 2 ms for low speeds

 

 

and to 4 ms for very low speeds. When P147 = 1, the nominal

 

 

measuring time is switched over to 4 ms for low speeds)

Caution:

When P146=1, the minimum measurable speed can be reduced by up to a factor of 4 as opposed to a 0 setting. However, this setting results in a longer actual speed sensing delay in the extended minimum speed range.

0 to 2

1

0 to 1

1

0 to 1

1

Ind: 4

P052

= 3

FS=2

P051

= 40

Type: O2

Offline

Ind: 4

P052

= 3

FS=0

P051

= 40

Type: O2

Offline

Ind: 4

P052

= 3

FS=0

P051

= 40

Type: O2

Offline