Fault

No.

 

Description

 

 

 

Cause as a function of fault value

 

 

Further information (r047.002 to r047.016)

 

 

(r047.001, r949.001 or r949.009 with acknowledged error)

 

 

 

 

 

 

 

 

 

 

F042

Tachometer fault

(active in operating states of – –, I, II)

A check is performed every 20ms to ensure that Actual speed (K0179) is > +5%

Actual EMF (K0287)

If the check result is incorrect for 4 times in succession, the fault message is activated.

The following rule applies:

 

100% actual speed

= maximum speed

100% actual EMF

= ideal average DC voltage at α 0, i.e. when the thyristor bridge is fully gated

The ideal DC voltage average value at α = 0 is P078.0013 2

π

The monitoring function is effective only if the EMF > a % of P078.0013 2

π

"a" is a percentage that can be set in parameter P357 (default setting 10%).

The monitoring function is effective only if the armature current is > 2% of the converter rated DC current set in r072.002.

Possible fault causes

Open circuit in tachometer or pulse encoder cable.

Tachometer of pulse encoder cable incorrectly connected.

Pulse encoder supply has failed.

Polarity for actual speed value (P743) is incorrectly set.

Armature circuit data (P110 und P111) are incorrectly set (execute current controller optimization run).

Tachometer or pulse encoder defective

Pulse encoder supply voltage is incorrectly set (P140)

The field polarity is not reversed by the external hardware when the field is reversed.

Fault value:

r047 Index 002 to 016:

 

 

 

 

1

Open circuit in tachometer or pulse encoder cable

i002

Actual speed value (K0179) in case of fault

 

 

 

 

2

Polarity of tachometer or pulse encoder is incorrect

i003

Actual EMF value (K0287) in case of fault

 

 

 

 

9-12