PNU

Description

Value range [Unit] Steps

No. indices Factory setting Type

See Change (Access / Status)

10.27 Configuring of torque shell input

P500

Source for torque setpoint for slave drive

*

Selection of the connector to be injected as the torque setpoint for a slave

BDS

drive

 

(G160)

0 = connector K0000

 

1 = connector K0001

 

etc.

 

 

P501

Source for additional torque setpoint

*

Selection of connector to be injected as the additional torque setpoint

BDS

0 = connector K0000

 

(G160)

1 = connector K0001

 

etc.

 

 

All connector numbers

1

All connector numbers

1

Ind: 2

P052

= 3

FS=170

P051

= 40

Type: L2

Offline

Ind: 2

P052

= 3

FS=0

P051

= 40

Type: L2

Offline

P502

Source for value to be added to speed controller output

*

Selection of connector to be injected as the value to be added to the speed

 

(G152)

controller output (in addition to friction and moment of inertia compensation)

 

 

0 = connector K0000

 

1 = connector K0001

 

etc.

 

 

P503

Multiplier for torque setpoint in slave mode

FDS

 

(G160)

 

All connector numbers

1

-300.00 to 300.00 [%] 0.01%

Ind: None

P052

= 3

FS=0

P051

= 40

Type: L2

Offline

Ind: 4

P052

= 3

FS=100.00

P051

= 40

Type: I2

on-line

10.28 Speed limiting controller

(see also Section 8, Sheet G160 of Operating Instructions 6RX1700-0AD**)

The output of the speed limiting controller comprises a positive (K0136) and a negative (K0137) torque limit. These limits are applied to the torque limitation

P509

Source for input quantity (n-act) of speed limiting controller

*

0 = connector K0000

(G160)

1 = connector K0001

 

 

etc.

 

 

P510

Source for pos. torque limit of speed limiting controller

*

Selection of the connector to be injected as the limit value for torque

 

(G160)

limitation 1

 

0 = connector K0000

 

1 = connector K0001

 

etc.

 

 

P511

Source for neg. torque limit of speed limiting controller

*

Selection of the connector to be injected as the limit value for torque

 

(G160)

limitation 2

0 = connector K0000

 

 

1 = connector K0001

 

etc.

 

 

P512

Maximum speed in positive direction of rotation

FDS

 

(G160)

 

P513

Maximum speed in negative direction of rotation

FDS

 

(G160)

 

P515

P gain of speed limiting controller

FDS

 

(G160)

 

All connector numbers

1

All connector numbers

1

All connector numbers

1

0.0to 199.9

[%]

0.1% of rated speed -199.9 to 0.0

[%]

0.1% of rated speed

0.10to 200.00

Ind: None

P052

= 3

FS=167

P051

= 40

Type: L2

Offline

 

 

 

Ind: None

P052

= 3

FS=2

P051

= 40

Type: L2

Offline

Ind: None

P052

= 3

FS=4

P051

= 40

Type: L2

Offline

Ind: 4

P052

= 3

FS=105.0

P051

= 40

Type: O2

Online

Ind: 4

P052

= 3

FS=-105.0

P051

= 40

Type: I2

Online

Ind: 4

P052

= 3

FS=3.00

P051

= 40

Type: O2

Online

SIEMENS Energy & Automation

10-53

SIMOREG DC Master Base Drive Panel Operating Instructions

 