10.46 Fault memory

r947

Fault memory

 

 

 

 

Display of fault messages generated in response to recent faults. A fault

(G189)

value and fault time is assigned to each fault number (see Section 10 for

 

details of fault numbers and fault values).The interrelationship between the

 

associated parameters is shown in the diagram below.

 

 

The fault numbers of the last (maximum 8) fault events are stored under the

 

indices of parameter P947. r947.001 displays the fault number of the current

 

(still not acknowledged) fault, index 9 displays the number of the most

 

recent acknowledged fault, index 17 the fault number of the second most

 

recent acknowledged fault, etc. An entry of "0" means that no "earlier" fault

 

has occurred. Since only one fault message can be stored with respect to

 

any fault event on the SIMOREG 6RA70, only indices 1, 9, 17, 25, 33, 41,

 

49 and 57 are relevant.

 

 

 

 

A fault value is assigned to each fault number in the corresponding index of

 

parameter r949. This provides further information about the nature of the

 

fault.

 

 

 

 

 

In addition, the fault time (the current reading of the hours run counter as

 

the fault occurred (r048)), is stored for each fault in r049. The data for the

 

current (not yet acknowledged) fault are stored as the "Hours run counter

 

reading" in index 1. The data for earlier, already acknowledged faults are

 

stored under the following indices.

 

 

 

 

r947

r949

r049

 

 

 

Fault number

Fault value

Fault time [h]

 

 

Index 1

Current

Current

Current

Index 1

 

 

0

0

1st acknowl.

Index 2

 

 

0

0

2nd acknowl.

Index 3

 

 

0

0

3rd acknowl.

Index 4

 

 

0

0

4th acknowl.

Index 5

 

 

0

0

5th acknowl.

Index 6

 

 

0

0

6th acknowl.

Index 7

 

 

0

0

7th acknowl.

Index 8

 

Index 9

1st acknowl.

1st acknowl.

 

 

 

 

0

0

 

 

 

 

0

0

 

 

 

 

0

0

 

 

 

 

0

0

 

 

 

 

0

0

 

 

 

 

0

0

 

 

 

 

0

0

 

 

 

Index 17

2nd acknowl.

2nd acknowl.

 

 

 

 

. . .

. . .

 

 

 

Plaintext information about the fault numbers is available under the

 

corresponding index of parameter r951.

 

 

r949

Fault value

 

 

 

 

Fault value of faults, allows more detailed diagnosis for a variety of

(G189)

parameters.

 

 

 

 

The fault values are stored in the same indices as the associated fault

 

numbers (r947) - see parameter r947.

 

 

 

 

 

 

 

 

r951

Fault text

 

 

 

 

 

 

 

 

 

P952

Number of faults

 

 

 

Settings:

0Deletes the entire fault memory (r947, r949 and r049) by resetting to 0

Note:

P952 cannot be reset while a fault is pending

>0 Display of the faults stored in the fault memory (r947, r949 and r049)

0 to 65535

1

0 to 65535

1

Ind: 64

P052 = 3

Type: O2

 

Ind: 64

P052

= 3

Type: O2

 

 

 

 

 

Ind: 101

P052

= 3

Type: O2

 

 

Ind: None

P052

= 3

FS=0

P051

= 40

Type: O2

Offline

SIEMENS Energy & Automation

10-89

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 210
Image 210
Siemens 6RA70 specifications 10-89, R947 Fault memory, R949 Fault value, R951 Fault text P952 Number of faults