10.30 Compensation of moment of inertia (dv/dt injection)

(see also Section 8, Sheet G153 of Operating Instructions 6RX1700-0AD**)

P540

Acceleration time

FDS

The acceleration time is the time that would be needed to accelerate the

drive from 0% to 100% of maximum speed (with no friction) at 100%

 

(G153)

converter rated DC current (armature) and 100% rated motor field current

(i.e. 100% flux). It is a measure of the moment of inertia on the motor shaft.

 

 

This parameter is set automatically during the optimization run for friction

 

and moment of inertia compensation (P051=28).

 

 

P541

P gain of acceleration

FDS

Proportional gain for "SAD-dependent acceleration" function (see also

(G153)

parameter P543)

 

 

P542

Time difference for dy/dt of ramp-function generator

FDS

Ramp-function generator:

Setting of dt for the output of dy/dt at a connector, i.e. at K0191, the change

 

(G136)

in the output quantity of the ramp-function generator (K0190) is output within

the period set in P542

 

Example: - The ramp-function generator is currently ramping up with a ramp-up time of P311=5s, i.e. a ramp-up operation from y=0% to y=100% takes 5s.

-A time difference dt of P542=2s is set.

-A dy/dt of 40% appears at connector K0191 since the dy within the set dt of 2 s equals (2s/5s)*100%..

 

(see also parameter P330)

 

 

 

P543

Threshold for SAD-dependent acceleration

FDS

With respect to the SAD-dependent acceleration function, only the

component of the speed controller setpoint/actual value difference which

 

(G153)

has an absolute value in excess of the threshold set in this parameter is

switched through (see also parameter P541).

 

 

Output (value to be multiplied by P541)

 

199.99%

 

 

negative

 

 

threshold

Input (setp./act. val. diff.)

 

-200.00% (-P543)

 

positive

199.99%

 

threshold

 

 

(P543)

 

 

-200.00%

 

 

 

P546

Filter time for compensation of moment of inertia

FDS

 

 

(G153)

 

 

0.00to 650.00

[s]

0.01s

0.00to 650.00

0.01to 300.00

[s]

0.01s

0.00to 100.00

[%]

0.01% of maximum speed

0 to 10000 [ms] 1ms

Ind: 4

P052

= 3

FS=0.00

P051

= 40

Type: O2

Online

Ind: 4

P052

= 3

FS=0.00

P051

= 40

Type: O2

Online

 

 

 

Ind: 4

P052

= 3

FS=0.01

P051

= 40

Type: O2

Online

Ind: 4

P052

= 3

FS=0.00

P051

= 40

Type: O2

Online

Ind: 4

P052

= 3

FS=0

P051

= 40

Type: O2

Online