PNU

Description

Value range [Unit] Steps

No. indices

See

Factory

Change

setting

(Access /

Type

Status)

10.41 Deactivation of monitoring functions

WARNING

If monitoring functions are deactivated, there may be a risk to the safety of operating personnel or of substantial property damage if a fault or error actually occurs!

P820

Deactivation of fault messages

*

The numbers of all fault messages to be deactivated must be entered in this

 

 

parameter. Fault numbers can be entered in any order. 0 must be entered

 

for any unused indices of the parameter.

 

Factory setting:

 

 

i001

= 7

(overvoltage)

 

i002

= 18

(short circuit at binary outputs)

 

i003

= 31

(monitoring of speed controller)

 

i004

= 35

(drive blocked)

 

i005

= 36

(armature current cannot flow)

 

i006

= 37

(I2t motor monitoring function has responded)

 

i007 to i099 = 0

 

 

 

P821

Deactivation of alarms

*

The numbers of all alarm messages to be deactivated must be entered in

 

 

this parameter. Alarm numbers can be entered in any order. 0 must be

 

entered for any unused indices of the parameter.

 

 

 

 

0 to 147

1

0 to 147

1

Ind: 99

P052

= 3

FS=

P051

= 40

see column

Online

on left

 

 

Type: O2

 

 

Ind: 99

P052

= 3

FS= 0

P051

= 40

Type: O2

Online

10.42 Compensation values

r824

A7006 compensation values

 

These data contain compensation values for the analog section of

 

electronics board A7006

 

 

P825

Offset compensation for actual field current channel

 

These data contain compensation values for the actual field current sensing

 

function. They are automatically set during "Restore factory settings"

 

(P051=21) and during the automatic offset compensation run (P051=22).

 

 

P826

Correction of natural commutation timing

(G163)

If there is a variation in the armature current peak value (in spite of a

 

constant firing angle), it can be corrected by offsetting the firing angle

 

reference time of the appropriate line phase in parameter P826. One line

 

phase (UV, UW, VW, VU, WU, WV) is assigned to each parameter index

 

(i001 to i006).

 

Increasing the parameter setting by a value of 1 corresponds to an increase

 

of 1.333 µs in the firing angle (0.024 degrees at 50Hz line frequency),

 

consequently reducing the armature current peak in the appropriate line

 

phase.

 

 

P826 is automatically set during the optimization run for precontrol and

 

current controller (armature and field) (P051=25) (only when U800=0; when

 

U800=1 or 2, parameters P826.001 to 006 are set to 0).

 

Caution:

 

 

Even an asymmetrical system causes variations in the magnitude of

 

armature current peaks. However, the system asymmetry may also change.

 

 

r827

Internal diagnosis

 

i001:

Number of write access operations to EEPROM

 

i002:

Number of Page-Write access operations to EEPROM

 

i003:

Counter for DUAL-PORT RAM timeouts

 

 

 

r828

MLFB data

 

 

These data contain details about the power section design (model)

 

 

r829

A7001 compensation values

 

These data contain compensation values for the analog section of

 

electronics board A7001

 

 

 

0 to 65535

1

13000 to 25000

1

-100 to 100 * 1.333 [µs]

1.333µs

0 to 65535

1

0 to 65535

1

0 to 65535

1

Ind: 10

P052

= 3

Type: O2

 

 

 

 

 

Ind: 3

P052

= 3

FS=19139

P051

= 40

Type: O2

Online

 

 

 

Ind: 6

P052

= 3

FS=0

P051

= 40

Type: I2

Online

Ind: 3

P052 = 3

Type: O2

 

 

 

Ind: 16

P052 = 3

Type: O2

 

 

 

Ind: 68

P052 = 3

Type: O2

 

SIEMENS Energy & Automation

10-87

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 208
Image 208
Siemens 6RA70 specifications Deactivation of monitoring functions, Compensation values, 10-87