P088

 

Brake closing time

0.00 to 10.00

Ind: None

P052 = 3

 

 

 

When the "Switch-on" or "Inching" or "Crawling" command is cancelled, or

[s]

FS=0.00

P051 = 40

 

(G140)

 

0.01s

Type: O2

Online

 

 

when the "Switch-on" command is not applied, or when the "Fast stop"

 

(G187)

 

 

 

 

 

 

 

 

 

command is input, the internal controller disabling signal, and thus the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

thyristor gating pulse disabling signal, is not actually activated after n<nmin

 

 

 

 

 

 

 

 

has been reached until the time delay set in this parameter has elapsed.

 

 

 

 

 

 

 

 

During this period, the drive continues to produce a torque (operating state

 

 

 

 

 

 

 

 

I, II or – –), so as to give the holding brake enough time to close.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P089

Maximum wait time for voltage to appear at power section

 

0.0 to 60.0

Ind: None

P052 = 3

 

 

 

When the line contactor has dropped out and the "Switch-on" or "Inching" or

 

[s]

FS=2.0

P051 = 40

 

 

 

 

0.1s

Type: O2

Online

 

 

 

"Crawling" command is applied, the converter waits in operating states o4

 

 

 

 

 

 

 

 

 

 

 

 

 

and o5 for voltage to appear at the power section, for the actual field current

 

 

 

 

 

 

 

 

 

value (K0265) to reach > 50% of the field current setpoint (K0268). The

 

 

 

 

 

 

 

 

 

corresponding fault message is activated if no power section voltage and no

 

 

 

 

 

 

 

 

 

field current is detected. This parameter specifies the maximum total delay

 

 

 

 

 

 

 

 

 

period in which the drive may dwell in operating states o4 and o5 (response

 

 

 

 

 

 

 

 

 

threshold for function which checks for voltage at power section, see

 

 

 

 

 

 

 

 

 

parameter P353).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P090

 

Stabilization time for line voltage

 

0.01 to 1.00

Ind: None

P052 = 3

 

 

 

When the line contactor has dropped out and the "Switch-on" or "Inching" or

 

[s]

FS=0.02

P051 = 40

 

 

 

 

0.01s

Type: O2

Online

 

 

 

"Crawling" command is applied, or after a phase failure has been detected

 

 

 

 

 

 

 

 

 

 

 

 

 

in the armature or field mains supply with active "Automatic restart" function

 

 

 

 

 

 

 

 

 

(P086>0), the converter dwells in operating state o4 and o5 until voltage

 

 

 

 

 

 

 

 

 

appears at the power section. Line voltage is not assumed to be applied to

 

 

 

 

 

 

 

 

 

the power terminals until the amplitude, frequency and phase symmetry

 

 

 

 

 

 

 

 

 

have remained within the permissible tolerance for a period exceeding the

 

 

 

 

 

 

 

 

 

setting in this parameter. The parameter applies to both the armature and

 

 

 

 

 

 

 

 

 

field power connections.

 

 

 

 

 

 

 

 

 

Caution:

 

 

 

 

 

 

 

 

 

 

The setting in P090 must be lower than the settings in P086 (except when

 

 

 

 

 

 

 

 

 

P086=0.0) and P089!

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P091

Setpoint threshold

 

0.00 to 199.99

 

Ind: 2

 

P052 = 3

 

 

 

i001:

Threshold for function "Switch on only if setpoint is low“

[%]

 

FS=

 

P051 = 40

 

 

 

0.01%

 

i001: 199.99

 

Online

 

 

 

 

The converter can be switched on only if a setpoint

 

 

 

 

 

 

 

 

 

i002: 0.00

 

 

 

 

 

 

K0193 P091.001 is applied to the ramp-function generator

 

 

 

 

 

 

 

 

 

 

 

 

Type: O2

 

 

 

 

 

 

input. If the applied setpoint is higher, the converter dwells in

 

 

 

 

 

 

 

 

 

 

state o6 after "switch-on" until the absolute setpoint value is

 

 

 

 

 

 

 

 

 

 

P091.001.

 

 

 

 

 

 

 

 

 

i002:

Threshold for function

 

 

 

 

 

 

 

 

 

 

"Automatic pulse disable if setpoint is low“ [SW 2.0 and later]

 

 

 

 

 

 

 

 

 

 

If n-set (K0193) and n-act (K0166) are less than P091.002,

 

 

 

 

 

 

 

 

 

 

the firing pulses are disabled and the drive goes into state o2.0.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 