PNU

 

Description

Value range

No. indices

See

 

 

 

 

 

[Unit]

Factory

Change

 

 

 

 

 

Steps

setting

(Access /

 

 

 

 

 

 

Type

Status)

 

P046

 

Binector display:

All binector numbers

Ind: 4

P052 = 3

*

 

i001:

Selection of binector displayed in r045.01

1

FS=0

P051 = 40

 

 

 

 

Type: L2

Online

 

(G121)

 

i002:

Selection of binector displayed in r045.02

 

 

 

 

 

 

 

 

i003:

Selection of binector displayed in r045.03

 

 

 

 

 

 

 

 

 

 

 

 

i004:

Selection of binector displayed in r045.04

 

 

 

 

 

 

 

 

 

 

 

r047

Display of fault diagnostic memory

 

 

Provides more detailed information about the cause of a fault after activation

 

of a fault message (see Section 10).

 

 

i001

Word 1 (fault value)

 

 

i002

Word 2

 

 

...

 

 

 

i016

Word 16 (fault number)

 

r048

Hours run

 

 

(G189)

Display of time (hours) in which drive has been operating in states I, II or - -.

All times of approx. 0.1 s are included in the count.

 

 

 

 

r049

Fault time

 

 

 

Display of time at which the current fault, and the last 7 acknowledged

(G189)

faults, were activated.

 

 

i001:

Current fault

hours

 

i002:

1st acknowledged fault

hours

 

i003:

2nd acknowledged fault

hours

 

i004:

3rd acknowledged fault

hours

 

i005:

4th acknowledged fault

hours

 

i006:

5th acknowledged fault

hours

 

i007:

6th acknowledged fault

hours

 

i008:

7th acknowledged fault

hours

P050

Language

 

 

*

Language of plaintext display on optional OP1S operator panel and in

 

 

DriveMonitor PC service routine

 

 

0:

German

 

 

1:

English

 

 

2:

Spanish

 

 

3:

French

 

 

4:

Italian

 

 

 

 

 

0 to 65535

1

0 to 65535 [hours]

1 hour

0 to 65535 [hours]

1 hour

0 to 4

1

Ind: 16

P052 = 3

Type: O2

 

Ind: None

P052 = 3

Type: O2

 

 

 

Ind: 8

P052 = 3

Type: O2

 

Ind: None

P052 = 3

FS=0

P051 0

Type: O2

Online

10.3Access authorization levels

P051

Key parameters

*

0

No access authorization

 

6Do not set (for use by DriveMonitor)

7Do not set (for use by DriveMonitor)

9Do not set (for use by DriveMonitor)

21Restore factory settings

All parameters are reset to their defaults (factory settings). Parameter P051 is then automatically reset to factory setting "40".

22Execute internal offset compensation (see Section 7.4)

25Optimization run for precontrol and current controller (armature and field) (see Section 7.5)

26Optimization run for speed controller (see Section 7.5)

27Optimization run for field weakening (see Section 7.5)

28Optimization run for compensation of friction and moment of inertia (see Section 7.5)

29Optimization run for the speed controller with an oscillating mechanical system (see Section 7.5)

40Access authorization to parameter values for authorized service personnel

P052

Selection of display parameters

*

0

0 Display only parameters that are not set to original factory

 

 

 

settings

 

1

Display only parameters for simple applications

 

3

Display all parameters used

see column on left

0, 1, 3

Ind: None

P052 = 3

FS=40

P051 0

Type: O2

Online

Ind: None

P052 = 3

FS=3

P051 0

Type: O2

Online

SIEMENS Energy & Automation

10-11

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 132
Image 132