Description

 

Value range

No. indices

See

 

 

 

 

[Unit]

Factory

Change

 

 

 

 

Steps

setting

(Access /

 

 

 

 

 

Type

Status)

 

o7.3

Waiting for completion of "Restore factory settings" operation.

 

 

 

 

o7.4

Waiting for switch-on command before execution of an

 

 

 

 

 

optimization run

 

 

 

 

 

o7.5

Wait for completion of "Read in parameter set" operation.

 

 

 

 

o7.6

Wait for completion of "Load MLFB" operation (performed at

 

 

 

 

 

factory)

 

 

 

 

 

o7.9

reserved for firmware download for optional supplementary

 

 

 

 

 

modules

[SW 2.0 and later]

 

 

 

 

o8

Waiting for acknowledgement of starting lockout

 

 

 

 

o8.0

Waiting for acknowledgement of starting lockout through input of

 

 

 

 

 

SHUTDOWN command (OFF1).

 

 

 

 

 

o8.1

Simulation operation active (see under U840) [SW1.7 and later]

 

 

 

 

o9

Fast stop (OFF3)

 

 

 

 

 

o9.0

Fast stop has been input via binector (acc. to selection in P658)

 

 

 

 

 

or control word, bit 2 (acc. to selection in P648).

 

 

 

 

o9.1

Fast stop has been input via binector (acc. to selection in P659).

 

 

 

 

o9.2

Fast stop has been input via binector (acc. to selection in P660).

 

 

 

 

o9.3

Fast stop is stored internally (memory can be reset by cancelling

 

 

 

 

 

FAST STOP command and entering SHUTDOWN).

 

 

 

 

o10

Voltage disconnection (OFF2)

 

 

 

 

 

o10.0

Voltage disconnection has been input via binector (acc. to

 

 

 

 

 

selection in P655) or control word, bit 1 (acc. to selection in

 

 

 

 

 

P648).

 

 

 

 

 

o10.1

Voltage disconnection has been input via binector (acc. to

 

 

 

 

 

selection in P656).

 

 

 

 

 

o10.2

Voltage disconnection has been input via binector (acc. to

 

 

 

 

 

selection in P657).

 

 

 

 

 

o10.3

E-Stop (safety shutdown) has been input via terminal 105 or 107

 

 

 

 

o10.4

Wait for receipt of a valid telegram on G-SST1 (only if telegram

 

 

 

 

 

failure time monitoring is set with P787 0)

 

 

 

 

 

o10.5

Waiting for receipt of a valid telegram on G-SST2 (only if

 

 

 

 

 

telegram failure time monitoring is set with P797 0)

 

 

 

 

o10.6

Waiting for receipt of a valid telegram on G-SST3 (only if

 

 

 

 

 

telegram failure time monitoring is set with P807 0)

 

 

 

 

o11

Fault

 

 

 

 

 

o11.0

= Fxxx Fault message is displayed, red LED lights up.

 

 

 

 

o12

Electronics initialization in progress

 

 

 

 

 

o12.1

Basic converter electronics initialization in progress

 

 

 

 

o12.2

Initialization of supplementary board in location 2 in progress

 

 

 

 

o12.3

Initialization of supplementary board in location 3 in progress

 

 

 

 

o12.9

Restructuring of parameters in non-volatile storage after

 

 

 

 

 

software update (takes approx. 15s)

 

 

 

 

 

o13

Software update in progress

 

 

 

 

 

o13.0

Waiting for arrival of start command from HEXLOAD PC routine

 

 

 

 

 

(press the DOWN key to abort this status and start a RESET)

 

 

 

 

o13.1

Deletion of Flash EPROM in progress

 

 

 

 

 

xxxxx

Display of address currently being programmed

 

 

 

 

o13.2

The Flash EPROM has been successfully programmed

 

 

 

 

 

(a RESET is performed automatically after approx. 1 second)

 

 

 

 

o13.3

Programming of the Flash EPROM has failed

 

 

 

 

 

(press UP key to return to operating state o13.0)

 

 

 

 

o14

Loading of boot sector in progress

 

 

 

 

 

 

(this operation is performed only in factory)

 

 

 

 

 

o15

Electronics not connected to voltage

 

 

 

 

 

 

Dark display: Waiting for voltage at terminals 5U1, 5W1

 

 

 

 

 

(electronics supply voltage).

 

 

 

 

 

 

 

 

 

 

 