Siemens 6RA70 specifications Control word, status word, 10-67

Models: 6RA70

1 232
Download 232 pages 59.99 Kb
Page 188
Image 188

PNU

Description

Value range [Unit] Steps

No. indices Factory setting Type

See Change (Access / Status)

10.35 Control word, status word

Selection of sources of control words 1 and 2

P648

Source for control word 1

*

Selection of connector to act as the source for control word 1.

BDS

0

= connector K0000

 

(G180)

...

 

 

8

= connector K0008

 

9

= parameters P654 to P675 are effective

(every individual bit of control word 1 is input by a binector)

10= connector K0010

etc.

P649

Source for control word 2

*

Selection of connector to act as the source for control word 2.

BDS

0

= connector K0000

 

(G181)

...

 

 

8

= connector K0008

 

9

= parameters P676 to P691 are effective

(every individual bit of control word 2 is input by a binector)

10= connector K0010

etc.

All connector numbers

1

All connector numbers

1

Ind: 2

P052

= 3

FS=9

P051

= 40

Type: L2

Offline

Ind: 2

P052

= 3

FS=9

P051

= 40

Type: L2

Offline

Display of control words 1 and 2

r650

Display of control word 1

 

 

 

 

 

 

(G180)

Mode of representation on operator panel (PMU):

 

 

 

 

 

 

 

 

 

 

15

14

13

12

11

10

9

8

 

7

6

5

4

3

2

1

0

Segments 0 to 15 correspond to bits 0 to 15 of the control word

 

Segment ON:

Corresponding bit is in log. "1" state

 

Segment OFF:

Corresponding bit is in log. "0" state

 

 

 

 

 

 

 

 

r651

Display of control word 2

 

 

 

 

 

 

(G181)

Mode of representation on operator panel (PMU):

 

 

 

 

 

 

 

 

 

 

 

 

15

14

13

12

11

10

9

8

 

 

7

6

5

4

3

2

1

0

Segments 0 to 15 correspond to bits 16 to 31 of the control word

Segment ON:

Corresponding bit is in log. "1" state

Segment OFF:

Corresponding bit is in log. "0" state

Ind: None

P052 = 3

Type: V2

 

Ind: None

P052 = 3

Type: V2

 

Display of status words 1 and 2

r652

(G182)

Display of status word 1

Mode of representation on operator panel (PMU):

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Segments 0 to 15 correspond to bits 0 to 15 of the status word

Segment ON:

Corresponding bit is in log. "1" state

Segment OFF:

Corresponding bit is in log. "0" state

Ind: None

Type: V2

P052 = 3

SIEMENS Energy & Automation

10-67

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 188
Image 188