PNU

Description

Value range [Unit] Steps

No. indices Factory setting Type

See Change (Access / Status)

P256

Field current controller reset time

 

FDS

This parameter is set automatically during the optimization run for precontrol

(G166)

and current controller (armature and field) (P051=25).

 

 

 

 

P257

Standstill field

 

FDS

Value to which the field current is reduced when "Automatic field current

reduction" function is parameterized (by means of P082=2) or with signal-

 

(G166)

driven selection of "Standstill excitation" function (selected in P692).

 

 

 

P258

Delay time with automatic field current reduction

 

FDS

Delay after which the field current is reduced to the value set in parameter

P257 with automatic or signal-driven "Field current reduction" function when

 

(G166)

the drive is stopped after operating state o7.0 or higher is reached.

 

 

 

P260

Filter time for setpoint for field current precontrol

[SW 1.9 and later]

FDS

Filtering of the field current setpoint at the input of the precontrol for the field

current controller.

 

 

 

(G166)

The purpose of this filter is to decouple the field current precontrol from the

 

field current controller.

 

P261

Filter time for setpoint for field current controller

[SW 1.9 and later]

FDS

Filtering of the field current setpoint at the input of the field current

controller.

 

 

 

 

 

(G166)

The purpose of this filter is to decouple the field current precontrol from the

 

field current controller.

 

 

 

 

P263

Input quantity for motor flux calculation

 

*

0

The input quantity for the motor flux calculation is the field

FDS

 

current controller actual value according to P612 (K0265), to be

(G166)

 

used in connection with a fully compensated DC machine

 

 

 

1The input quantity for the motor flux calculation is the precontrol output for the EMF controller (K0293)

(exception: Field current controller setpoint (K0268) with active standstill field or with disabled field pulses), to be used in connection with an non-compensated DC machine. The EMF controller must be active when this setting is selected (EMF controller compensates the armature reaction).

2The input quantity for the motor flux calculation is the field current controller setpoint (K0268). Advantage: Quantities derived from the setpoint are generally "steadier" than those derived from actual values.

P264

Set field current controller P component to zero

*

0

Set controller P component to zero (i.e. to obtain pure I

FDS

 

controller)

(G166)

 

1

Controller P component is active

 

P265

Source for selection of external field current monitoring signal

*

[SW 1.9 and later]

BDS

Selection of the binector to supply the field monitoring signal when an

(G167)

external field device is used.

(status "1" = field current is o.k., If > If-min)

 

 

The converter waits for this signal in state o5.0 as part of the power ON

 

routine. If the signal disappears during operation, the drive is shut down with

 

fault message F005, fault value 4.

 

0 = binector B0000

 

1 = binector B0001

 

etc.

0.001 to 10.000 [s]

0.001s

0.0to 100.0

[%]

0.1% of P102

0.0to 60.0

[s]

0.1s

0 to 10000 [ms] 1ms

0 to 10000 [ms] 1ms

0 to 2

1

0 to 1

1

All binector numbers 1

Ind: 4

P052

= 3

FS=0,200

P051

= 40

Type: O2

Online

 

 

 

Ind: 4

P052

= 3

FS=0.0

P051

= 40

Type: O2

Online

 

 

 

Ind: 4

P052

= 3

FS=10.0

P051

= 40

Type: O2

Online

 

 

 

Ind: 4

P052

= 3

FS=0

P051

= 40

Type: O2

on-line

 

 

 

Ind: 4

P052

= 3

FS=0

P051

= 40

Type: O2

on-line

 

 

 

Ind: 4

P052

= 3

FS=1

P051

= 40

Type: O2

Offline

Ind: 4

P052

= 3

FS=1

P051

= 40

Type: O2

Offline

 

 

 

Ind: 2

P052

= 3

FS=1

P051

= 40

Type: L2

off-line

SIEMENS Energy & Automation

10-37

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 158
Image 158
Siemens 6RA70 specifications 10-37