Siemens 6RA70 specifications 10-64

Models: 6RA70

1 232
Download 232 pages 59.99 Kb
Page 185
Image 185

 

PNU

 

Description

Value range

No. indices

See

 

 

 

 

 

[Unit]

Factory

Change

 

 

 

 

Steps

setting

(Access /

 

 

 

 

 

Type

Status)

 

P627

 

Source for input of D element

All connector

Ind: None

P052

= 3

*

 

Selection of connector to be injected as the input signal for the D element

numbers

FS=178

P051

= 40

 

 

 

1

Type: L2

Offline

 

(G152)

 

 

 

 

0 = connector K0000

 

 

 

 

 

 

 

1 = connector K0001

 

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

P628

 

Source for input of band-stop filter 1

All connector

Ind: None

P052

= 3

*

 

Selection of connector to be injected as the input signal for band-stop filter 1

numbers

FS=179

P051

= 40

 

(G152)

 

1

Type: L2

Offline

 

 

0 = connector K0000

 

 

 

 

 

 

 

1 = connector K0001

 

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

P629

 

Source for band-stop filter 2

All connector

Ind: None

P052

= 3

*

 

Selection of connector to be injected as the input signal for band-stop filter 2

numbers

FS=177

P051

= 40

 

(G152)

 

1

Type: L2

Offline

 

 

0 = connector K0000

 

 

 

 

 

 

 

1 = connector K0001

 

 

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

 

Speed controller droop

P630

*

(G151)

Source for influencing quantity for speed droop

Selection of connector to be injected as the influencing quantity

0 = connector K0000

1 = connector K0001 etc.

All connector numbers

1

Ind: None

FS=162

Type: L2

P052 = 3

P051 = 40 Offline

Setting the speed controller I component

Function: When the binector selected in P695 switches state from log. "0" to log. "1", the I component of the speed controller is set to the

 

value of the connector selected in P631.

 

 

 

 

With this function it is possible, for example, to use the same signal (binector) to control controller enabling commands and

 

setting of the I component.

All connector

 

 

P631

Source for setting value for speed controller integrator

Ind: None

P052 = 3

*

Selection of connector to be injected as the setting value for the I

numbers

FS=0

P051 = 40

 

1

Type: L2

Offline

(G152)

component

 

 

 

 

 

 

 

 

0 = connector K0000

 

 

 

 

1 = connector K0001

 

 

 

 

etc.

 

 

 

 

 

 

 

 

Setting values for configuring the setpoint processing function and ramp-function generator

Limitation at ramp-function generator output (setpoint limitation)

(see also Section 8, Sheet G136 of Operating Instructions 6RX1700-0AD**)

The effective limitations are:

Upper limit:

Minimum value of P300 and the four connectors selected with P632

 

 

 

 

Lower limit:

Maximum value of P301 and the four connectors selected with P633

 

 

 

 

Note:

The limiting values for both the positive and negative setpoint limits can have a positive or negative sign. The negative setpoint

 

limit, for example, can therefore be parameterized to a positive value and the positive setpoint limit to a negative value.

P632

Source for variable positive limitation at ramp-function generator

All connector

 

Ind: 4

P052 = 3

*

output

numbers

 

FS=1

P051 = 40

(G137)

Selection of connectors to be injected at the variable positive limitation at

1

 

Type: L2

Offline

 

 

 

 

 

the ramp-function generator output (setpoint limitation).

 

 

 

 

 

0 = connector K0000

 

 

 

 

 

1 = connector K0001

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

P633

Source for variable negative limitation at ramp-function generator

All connector

 

Ind: 4

P052 = 3

*

output

numbers

 

FS=9

P051 = 40

(G137)

Selection of connectors to be injected at the variable negative limitation at

1

 

Type: L2

Offline

 

the ramp-function generator output (setpoint limitation).

 

 

 

 

 

0

= connector K0000

 

 

 

 

 

...

 

 

 

 

 

 

8

= connector K0008

 

 

 

 

 

9 = value as set in parameter P632 (1)

 

 

 

 

 

10 = connector K0010

 

 

 

 

 

etc.

 

 

 

 

 

 

 

 

 

 

 

10-64

 

 

 

SIEMENS Energy & Automation

 

 

SIMOREG DC Master Base Drive Panel Operating Instructions

Page 185