PNU

Description

Value range [Unit] Steps

No. indices Factory setting Type

See Change (Access / Status)

P714

Source for selection of sign reversal at "Analog selectable input 1"

*

Selection of binector to control sign reversal at the analog input ("1" state

 

(G113)

= reverse sign)

 

 

0 = binector B0000

 

1 = binector B0001

 

etc.

 

 

P715

Filtering time for "Analog selectable input 1"

(G113)

Note: Hardware filtering of approximately 1 ms is applied as standard.

 

P716

Source for enabling of "Analog selectable input 1"

*

Selection of binector to control enabling of the analog input ("1" state =

 

(G113)

enabled)

 

 

0 = binector B0000

 

1 = binector B0001

 

etc.

 

 

P717

Resolution of "Analog selectable input 1"

*

See P707

(G113)

 

All binector numbers

Ind: None

P052

= 3

1

FS=0

P051

= 40

 

Type: L2

Offline

0 to 10000

Ind: None

P052

= 3

[ms]

FS=0

P051

= 40

1ms

Type: O2

Online

All binector numbers

Ind: None

P052

= 3

1

FS=1

P051

= 40

 

Type: L2

Offline

10 to 14

Ind: None

P052

= 3

[Bit]

FS=12

P051

= 40

1 bit

Type: O2

Offline

Analog input terminals 8 / 9 (analog selectable input 2)

P721

Normalization of "Analog selectable input 2"

FDS

This parameter specifies the percentage value which is generated for an

input voltage of 10V (or an input current of 20mA) at the analog input.

 

(G114)

The following generally applies:

 

For voltage input:

 

 

P721 [%] =10 V Y

X .. Input voltage in volts

 

 

X

Y .. % value which is generated for input

 

 

 

 

With current input:

voltage X

 

 

 

P721 [%] = 20 mA Y

X .. Input current in mA

 

 

X

Y .. % value which is generated for input

 

 

 

 

 

 

current X

 

 

P722

Offset for "Analog selectable input 2"

(G114)

 

 

 

P723

Mode of signal injection at "Analog selectable input 2"

*

0 =

Injection of signal with sign

 

(G114)

1 =

Injection of absolute value of signal

2 =

Injection of signal with sign, inverted

 

 

3 =

Injection of absolute value of signal, inverted

 

 

P724

Source for selection of sign reversal at "Analog selectable input 2"

*

Selection of binector to control sign reversal at the analog input ("1" state

 

(G114)

= reverse sign)

 

 

 

 

 

0 = binector B0000

 

 

1 = binector B0001

 

 

etc.

 

 

 

 

P725

Filtering time for "Analog selectable input 2"

(G114)

Note: Hardware filtering of approximately 1 ms is applied as standard.

 

 

 

P726

Source for enabling of "Analog selectable input 2"

*

Selection of binector to control enabling of the analog input ("1" state =

 

(G114)

enabled)

 

 

 

 

 

0 = binector B0000

 

 

1 = binector B0001

 

 

etc.

 

 

 

 

 

 

-1000.0 to 1000.0

Ind: 4

P052

= 3

[%]

FS=100.0

P051

= 40

0.1%

Type: I2

Online

-200.00 to 199.99

Ind: None

P052

= 3

[%]

FS=0.00

P051

= 40

0.01%

Type: I2

Online

0 to 3

Ind: None

P052

= 3

1

FS=0

P051

= 40

 

Type: O2

Offline

All binector numbers

 

 

 

Ind: None

P052

= 3

1

FS=0

P051

= 40

 

Type: L2

Offline

0 to 10000

 

 

 

Ind: None

P052

= 3

[ms]

FS=0

P051

= 40

1ms

Type: O2

Online

All binector numbers

Ind: None

P052

= 3

1

FS=1

P051

= 40

 

Type: L2

Offline

SIEMENS Energy & Automation

10-73

SIMOREG DC Master Base Drive Panel Operating Instructions

 

Page 194
Image 194
Siemens 6RA70 specifications 10-73