3... INTERFACE MODULES

MLIM-1; FOUR CHANNEL ANALOG INTERFACE MODULE

Overview:

The MLIM-1 is a four channel add-on Interface Module for use in conjunction with the OMP-MODL System Base.

NOTE: The MLAD-1 module of the System Base includes the functionality of the MLIM-1 in additon to its other functions. This section’s configuration and operation instructions pertain to both the MLIM-1 add-on module and the MLAD-1 component of the System Base.

Each of the four channels can be individually programmed for any combination of the following signal types and input ranges with HyperWare software (via HyperNet) and hardware Configuration Switches (located on the Interface Module).

Thermocouple:

Type

Color (USA)

Range (F)

Range (C)

 

 

 

 

J

white/red

-60 to 1400F

-50 to 760C

 

 

 

 

K

yellow/red

32 to 2500F

0 to 1370C

 

 

 

 

E

purple/red

-150 to 1830F

-100 to 1000C

 

 

 

 

T

blue/red

-250 to 750F

-160 to 400C

 

 

 

 

R

black/red

32 to 1830F

0 to 1000C

 

 

 

 

S

black/red

32 to 3182F

0 to 1750C

 

 

 

 

Table 3... -1: Thermocouple input types and ranges

DC Voltage:

Full Scale (FS) ranges:

Icon

Full Scale Input Ranges

 

 

 

 

 

 

VDC-LO

+/- 20mV

+/-40mV

+/-50mV

+/-60mV

+/-100mV

 

 

 

 

 

 

 

+/-200mV

+/-1V

+/-2V

 

 

 

 

 

 

 

 

VDC-MED

+/-5 V

+/- 10V

 

 

 

 

 

 

 

 

 

VDC-HI

+/- 3V

+/-15V

+/-30V

 

 

 

 

 

 

 

 

Table 3... -2: DC Voltage input ranges

Input Impedance for the 5V, 10V, and 30V ranges is >2.5Megohm. All other range’s input impedance is > 10 Megohm.