Charge Refrigerant into Machine
CAUTION ! CAUTION
The transfer, addition, or removal of refrigerant in spring isolated machines may place severe stress on external piping if springs have not been blocked in both up and down directions.
The standard 19XL machine will have the refrigerant already charged in the vessels. The
19XL may be ordered with a nitrogen holding charge of 15 psig (103 kPa). Evacuate the entire machine, and charge machine from refrigerant cylinders.
19XL Machine Equalization without Pumpout Unit
WARNING ! WARNING
When equalizing refrigerant pressure on the 19XL machine after service work or during the initial machine