g. Open valves 2 and 5.

Valve

1a

1b

2

3

 

4

5

6

7

8

11

12

13

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Condition

 

 

 

C

 

C

 

 

C

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

h. Turn on pumpout condenser water.

 

 

 

 

 

 

 

 

 

i.

Run the pumpout compressor until the storage tank pressure reaches 5 psig (34 kPa)

 

(18 in. Hg [40 kPa absolute] if repairing the tank).

 

 

 

 

 

 

 

j.

Turn off the pumpout compressor.

 

 

 

 

 

 

 

 

 

 

k.

Close valves 1a, 1b, 2, 5, and 6.

 

 

 

 

 

 

 

 

 

 

l.

Turn off pumpout condenser water.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valve

1a

1b

2

3

 

4

5

6

7

8

11

12

13

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Condition

C

C

C

C

 

C

C

C

C

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 188
Image 188
Carrier PC211 specifications Open valves 2