g. Open valves 2 and 5.
h. Turn on pumpout conden s er wat er.
i. Run the pumpout compress o r until the storage tank pr es s u re reaches 5 psig (34 kPa)
(18 in. Hg [40 kPa absolut e] if repairing the tank).
j. Turn off the pumpout compressor.
k. Close valves 1a, 1b, 2, 5, and 6.
l. Turn off pumpout conden ser water.
Valve 1a 1b 2 3 4 5 6 7 8 11 12 13 14
Condition CC CC
Valve 1a 1b 2 3 4 5 6 7 8 11 12 13 14
Condition CCCCCCCCC