Table 10K — Machine Protect Limit Faults (Continued)
WARNING ! WARNING
Excessive numbers of the same fault can lead to severe machine damage.
Seek service expertise.
Primary | Secondary | Alarm Message/ | Additional Cause/Remedy | |||||||||
Message | Message | Primary Cause | ||||||||||
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
Protective | CCN Override Stop | CHIL S S CCN Over- | CCN has signaled machine to stop. Reset | |||||||||
|
|
|
|
|
|
|
|
|
|
| ||
| ride Stop while in LOCAL | and restart when ready. If the signal was | ||||||||||
Limit |
| run mode. | sent by the LID, release the Stop signal | |||||||||
|
|
|
|
|
|
|
|
|
|
| on STATUS01 table. | |
|
|
|
|
|
|
|
|
|
|
|
| |
Protective | Spare Safety Device | SRP |
|
| PL Spare Safety | Spare safety input has tripped or factory- | ||||||
Limit |
| Fault: Check contacts. | installed jumper not present. | |||||||||
|
|
|
|
|
|
|
|
| ||||
Protective | Excessive Motor | CA P [VALUE] | Check motor current for proper calibra- | |||||||||
|
|
|
|
|
|
| ||||||
Amps | exceeded limit of | tion. Check guide vane drive and actuator | ||||||||||
Limit |
| [LIMIT]*. High Amps; | for proper operation. | |||||||||
|
| Check guide vane drive. |
| |||||||||
|
|
|
|
|
|
|
| |||||
Protective | Excessive Compr | Compressor Surge: | Check condenser flow and temperatures. | |||||||||
Surge | Check condenser water | Check configuration of surge protection. | ||||||||||
Limit | ||||||||||||
| temp and flow. |
| ||||||||||
|
|
| ||||||||||
|
|
|
|
|
|
|
| |||||
Protective | Starter Fault | STR FLT Starter Fault: | Check starter for possible ground fault, | |||||||||
|
|
|
|
|
|
|
|
|
|
| ||
| Check starter for fault | reverse rotation, voltage trip, etc. | ||||||||||
Limit |
| |||||||||||
| source. |
| ||||||||||
|
|
| ||||||||||
|
|
|
|
|
|
|
| |||||
Protective | Starter Overload Trip | STR FLT Starter Over- | Reset overloads and reset alarm. Check | |||||||||
|
|
|
|
|
|
| ||||||
| load Trip: Check amps | motor current calibration or overload cali- | ||||||||||
Limit |
| calibration/reset over- | bration (do not | |||||||||
|
| load. |
| |||||||||
|
|
|
|
|
| |||||||
Protective | Transducer Voltage | V REF [VALUE] | Check transformer power (5 vdc) supply | |||||||||
|
|
|
|
| ||||||||
Fault | exceeded limit of | to transducers. Power must be 4.5 to 5.5 | ||||||||||
Limit |
| [LIMIT]*. Check trans- | vdc. | |||||||||
|
| ducer power supply. |
| |||||||||
|
|
|
|
|
| |||||||
Protective | Low Oil Pressure | Low Oil Pressure | Check the oil pressure switch for proper | |||||||||
| [OPEN]: Check oil pres- | operation. Check oil pump for proper | ||||||||||
Limit |
| sure switch/pump and | pressure. Check for excessive refrigerant | |||||||||
|
| 2C aux. | in oil system. | |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE] is the actual temperature, pressure, voltage, etc., at which the control tripped.