Example 4 — Setpoint Display Screen

To access this display from the LID default screen:

1.Press MENU.

2.Press SETPOINT.

Table 2, Example 4 — Setpoint Display Screen

Description

Configurable

Units

Reference Point

Default Value

Range

Name

 

 

 

 

 

 

 

 

 

 

Base Demand Limit

40-100

%

DLM

100

 

LCW Setpoint

20-120 (–6.7-48.9)

DEG F (DEG C)

lcw sp

50.0

(10.0)

ECW Setpoint

20-120 (–6.7-48.9)

DEG F (DEG C)

ecw sp

60.0

(15.6)

ICE BUILD Setpoint

20- 60 (–6.7-15.6)

DEG F (DEG C)

ice sp

40.0

( 4.4)

 

 

 

 

 

 