seconds may be chosen as need ed (typically 20 to 30 second s are used).
When the timer has bee n set, check that the s tarter, (with relay 1CR closed, goes thro ugh a
complete and proper start cycle.
Benshaw, Inc. Solid-S tate Starter
1. Check that all wiring connec tions are prope rly terminated to the starter.
2. Verify that the ground wi re to the starter is insta lled properly and is of su ff ic i ent size.
3. Verify that the motor s ar e pr o perly grounded to the st ar t er.
4. Check that all of the rela ys are properly seated in t heir sockets.
5. Verify that the proper ac input voltage i s brought into the starter per the certified d rawings.
6. Verify the initial fact ory settings of the star t ing torque and ramp potent iometers are set per
the note on the schemati c for the starters.
Note: The potentiometers are located at the lower left han d corner on the circuit bo ard
mounted in front of the star t er power stack (Figure 30 and Figure 31).
This equipment is at line voltage when AC power is connected. Pressing the
STOP button does not remove voltage. Use caution when adjusting the potenti-
ometers on the equip men t.
WARNING !WARNING