midnight to 3:00 a.m. weekend cool-down schedule.

Note: This schedule is for illustration only, and is not intended to be a recommended schedule for chiller operation.

PSIO Software Version 08 and Lower

Whenever the chiller is in the LOCAL mode, the machine will start when the Occupancy Schedule 01 indicates OCCUPIED. When in the CCN mode, Occupancy Schedule 02 is used.

PSIO Software Version 09 and Higher

The Local Time Schedule is still the Occupancy Schedule 01. The Ice Build Time Schedule is Schedule 02 and the CCN Default Time Schedule is Schedule 03. The CCN schedule number is defined on the Config table in the Equipment Configuration table. The schedule number can change to any value from 03 to 99. If this schedule number is changed on the Config table, the operator must use the Attach to Network Device table to upload the new number into the Schedule screen. See Figure 17.

Page 78
Image 78