Example 2 — Status02 Dis pl ay Screen

To access this display f ro m the LID default screen:
1. Press MENU.

2. Press STATUS.

3. Scroll down to highlight STATUS02.

4. Press SELECT.

Note: All values are variables available for read operation to a CCN. Descriptions shown with (*) support

write operations from the LID o nly.

Table 2, Example 2 — Status02 Display Screen

Description Point Type Units Reference Point

Name (Alarm

History)

Input Output

Hot Gas Bypass Relay
*Chilled Water Pump
Chilled Water Flow
*Condenser Water Pump
Condenser Water Flow
Compressor Start Relay
Compressor Start Contac t
Compressor Run Contact
Starter Fault C ontact
Pressure Trip Contact
Single Cycle Dropout
Oil Pump Relay
Oil Heater Relay
Motor Cooling Relay
*Tower Fan Relay
Compr. Shunt Trip Relay
Alarm Relay
Spare Prot Lim it Input
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
OFF/ON
OFF/ON
NO/YES
OFF/ON
NO/YES
OFF/ON
OPEN/CLOSED
OPEN/CLOSED
OPEN/CLOSED
OPEN/CLOSED
NORMAL/ALARM
OFF/ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
NORMAL/ALARM
ALARM/NORMAL
HGBR
CHWP
EVFL
CDP
CDFL
CMPR
1CR AUX
RUN AUX
STR FLT
PRS TRIP
V1 CYCLE
OILR
OILH
MTRC
TFR
TRIPR
ALM
SPR PL