Example 2 — Status02 Display Screen

To access this display from the LID default screen:

1.Press MENU.

2.Press STATUS.

3.Scroll down to highlight STATUS02.

4.Press SELECT.

Table 2, Example 2 — Status02 Display Screen

Description

Point Type

 

Units

Reference Point

 

 

Name (Alarm

Input

Output

 

 

History)

 

 

 

 

 

Hot Gas Bypass Relay

 

X

OFF/ON

HGBR

*Chilled Water Pump

X

X

OFF/ON

CHWP

Chilled Water Flow

X

NO/YES

EVFL

 

*Condenser Water Pump

X

OFF/ON

CDP

 

Condenser Water Flow

X

NO/YES

CDFL

 

Compressor Start Relay

 

OFF/ON

CMPR

Compressor Start Contact

X

 

OPEN/CLOSED

1CR

AUX

Compressor Run Contact

X

 

OPEN/CLOSED

RUN

AUX

Starter Fault Contact

X

 

OPEN/CLOSED

STR

FLT

Pressure Trip Contact

X

 

OPEN/CLOSED

PRS

TRIP

Single Cycle Dropout

X

 

NORMAL/ALARM

V1 CYCLE

Oil Pump Relay

 

X

OFF/ON

OILR

 

Oil Heater Relay

 

X

OFF/ON

OILH

 

Motor Cooling Relay

 

X

OFF/ON

MTRC

*Tower Fan Relay

 

X

OFF/ON

TFR

 

Compr. Shunt Trip Relay

 

X

OFF/ON

TRIPR

Alarm Relay

 

X

NORMAL/ALARM

ALM

 

Spare Prot Limit Input

X

 

ALARM/NORMAL

SPR PL

 

 

 

 

 

 

Note: All values are variables available for read operation to a CCN. Descriptions shown with (*) support

write operations from the LID only.

Page 254
Image 254
Carrier PC211 specifications Example 2 Status02 Display Screen